beautypg.com

6 key switch output interface, 6 key switch output interface -13, Dc24v gp – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 42: Key_no key_nc

background image

Chapter 2 Specifications

2-13

With the GP unit incorporating an emergency switch, the emergency switch activates the contact output, when

the emergency switch is enabled. To reset the emergency stop status (lock status), pull the button forward, or

turn the button in the direction indicated by arrow.

When the emergency switch is pressed, ON/OFF status of the EMG0 to EMG2 signals are as follows:

( ) indicates contact status.

2.3.6

Key Switch Output Interface

Turning OFF GP unit with the key switch

Turning ON GP unit with the key switch

Emergency Stop Reset

Emergency Stop

EMG0

0 (OFF)

1 (ON)

EMG1

1 (ON)

0 (OFF)

EMG2

1 (ON)

0 (OFF)

These signal lines must be disconnected (NC) when a GP unit without an emergency switch is

used.

Cable Color/Marking

Color, Number

Signal Name

Description

Orange/None

KEY_NC

Key Switch b-contact (normally closed)

Rating: DC24V, 300 mA

Orange/Black 1

KEY_NO

Key Switch a-contact (normally open)

Rating: DC24V, 300 mA

When the key is not turned to ON or OFF, either the “KEY_NO” or the “KEY_NC” signal is

ON. These signals will not simultaneously turn OFF.

These signal lines must be disconnected (NC) when a GP unit without a key switch is used.

EMG2A
EMG1A
EMG0A

EMG0B
EMG1B
EMG2B

DC24V

GP

OFF

ON

KEY_NO

KEY_NC

GP3000H Cable

DC24V

GP

OFF

ON

KEY_NO

KEY_NC

GP3000H Cable