Grounding, Input/output signal line cautions – Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 40
Chapter 2 Specifications
2-11
Grounding
This section describes the precautions for grounding the GP unit.
• When supplying power to the GP unit, be sure to separate the
input/output and power lines, as shown. [diagram (a)]
• If exclusive grounding is not possible, use a common
grounding point. [Diagram (b)] A D-type grounding or equiva-
lent should be used for the grounding point.
Input/Output Signal Line Cautions
•
All GP Input and Output signal lines must be separated from all operating circuit (power) cables.
•
If this is not possible, use a shielded cable and ground the shield.
Do not use common grounding, since it can lead to an accident or machine breakdown.
• Check that the grounding resistance is
100Ω or less.
• FG and SG terminals are internally
connected in the GP. When connecting
an external device to the GP using the
SG terminal, be sure to check that no
short-circuit loop is created when you
setup the system.
• The grounding wire should have a cross
sectional area greater than 2mm
2
Create the grounding point as close to
the GP unit as possible, and make the
wire as short, as possible. When using
a long grounding wire, replace the thin
wire with a thicker wire, and place it in a
duct.
•
If the equipment does not function properly
when grounded, disconnect the ground wire
from the FG terminal.
(a) Exclusive Grounding (BEST)
(b) Exclusive Grounding (OK)
(C) Common Grounding (Not OK)
GP
GP
Other
Equipment
Other
Equipment
GP
Other
Equipment
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"