Chapter 1 introduction – E-Mon E-PS-S-HV-RTU User Manual
Page 8

Chapter 1 Introduction
8
PowerSmart Socket Power Quality Meter
Chapter 1
Introduction
The
PowerSmart Socket PQM
The PowerSmart Socket PQM is especially designed for utility,
industrial and commercial billing metering with high
requirements to reliability of power quality monitoring and
availability of the device.
The
PowerSmart Socket PQM
is an electronic revenue-
accuracy multi-rate polyphase static meter integrated with a
multi-function powermeter, an EN50160 power quality
recorder, a digital fault recorder and a programmable logical
controller, and provided with a wide range of digital I/O and
communication options.
A high-contrast graphical LCD display with backlight allows
easy local meter readings and servicing. Three serial
communication ports (infrared and RS232/RS485), a USB
port, Ethernet and a wireless GSM/GPRS modem allow local
and remote automatic meter readings and setup though the
supplemental
communication
software
or
user
data
acquisition software
Meter Highlights
EN 50160 Power Quality Recorder
A full-featured programmable power quality recorder provides
EN 50160 compliance statistics and reports.
Fast Transient Recorder
An optional high-voltage fast transient recorder (available
with the transient add-on module) detects impulsive and low
frequency oscillatory transient overvoltages with peaks up to
2kV and durations from 20 microseconds.
Digital Fault Recorder
An embedded fault recorder is capable of recording fault
currents up to 50 amps.