Chapter 5 Configuring the PowerSmart Socket PQM
Configuring the EN50160
128
PowerSmart Socket Power Quality Meter
conventional waveforms to Waveform log #1 or #2,
then a second longer waveform will be also recorded,
synchronized with the fast transient waveform.
You can temporary disable the PQ recorder in your meter.
To enable or disable the PQ recorder:
1. Check or uncheck the Recorder Enabled checkbox.
2. Send your setting to the device.
Note that disabling the PQ recorder in your meter does not
affect the evaluation and recording of the EN50160 statistics.
Indication of Power Quality Events
When the PQ recorder detects a power quality fault, it
generates the specific internal event “PQ EVENT” that can be
monitored through a control setpoint. The event is asserted
all the time while the fault condition exists. The “PQ EVENT”
trigger can be used to give a power quality fault indication via
relay contacts, or can be combined using the AND operator
with timer ticks for periodic data recording at the time of the
fault to produce voltage trending charts.
EN50160 Harmonics Limits Setup
This setup allows you to adjust compliance limits for
harmonic and interharmonic voltages.
To change the default limits in your device:
1. Select Memory/Log from the Meter Setup menu, and
then click on the EN50160 Harmonics Setup tab.
2. Adjust limits you want to change.
3. Download your setup to the device.