Configuring the fault recorder – E-Mon E-PS-S-HV-RTU User Manual

Page 121

background image

Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Recorders

PowerSmart Socket Power Quality Meter

121

Configuring the Fault Recorder

The Fault recorder automatically records all fault events to
the Fault log file. It can be triggered via the embedded fault
detector, or externally through any of the 8 digital inputs.

The Fault recorder can be globally disabled or enabled in your
meter.

The Fault recorder setup allows you to adjust thresholds and
hysteresis for different fault triggers, and to define the
waveform and data log options for synchronous recording
during fault events.

To configure the Fault recorder:

1. Select Memory/Log from the Meter Setup menu, and

then click on the Fault Recorder tab.

2. Enable fault triggers suitable for your application.

3. If you wish to change the default settings, adjust

thresholds and hysteresis for your fault triggers.

4. Select the waveform and data logging options for

fault events.

5. Download your setup to the device.

The following table lists available Fault recorder options.

Option

Range

Default

Description

Thresholds

Threshold, % 0-200.0%

Defines the operating threshold for a fault trigger in
percent of the nominal (reference) value

Threshold,
secondary

Shows the setup value in secondary units for the
selected operating threshold