E-Mon E-PS-S-HV-RTU User Manual
Page 72

Chapter 5 Configuring the PowerSmart Socket PQM
Configuring Communications
72
PowerSmart Socket Power Quality Meter
The server’s IP address, port number and starting Modbus
register address are programmable in the meter.
The following table lists available options.
Parameter
Options
Default
Description
Client Enabled
NO, YES
NO
Enables operations of the
notification client
Server IP Address
192.168.0.3
The IP address of the
notification server
Server Port
0-65535
502
The TCP service port of the
notification server
Message Exchange
Address
0-65535
1000
Connection via Network Ethernet,
GPRS/Modem
Automatically selected
depending on the network
module installed
Client connections are triggered via programmable setpoints.
To send event notifications to a server, configure a setpoint
to respond to desired triggers or to periodic time events and
add the "Send notification" action to the end of the setpoint
actions list (see
Using Control Setpoints
).
Setpoint operation events triggered by regular analog and
digital triggers are reported twice - when the event starts and
when it ends, except of the pulsed events and time triggers
that will be reported once.
In case of triggering notifications with events generated by
the PQ and Fault recorders, like the PQ EVENT, FAULT EVENT,
EXTERNAL TRIGGER or FAULT DETECTED triggers, the
recorded power quality or/and corresponding fault events are
reported instead of setpoint-triggered notifications. If regular
triggers are added to the setpoint triggers list, then the
setpoint operation events will also be reported.