Display features, No load/power flow direction indicator, Phase presence indicators – E-Mon E-PS-S-HV-RTU User Manual
Page 35: Backlight

Chapter 3 Using Front Display
Display Operations
PowerSmart Socket Power Quality Meter
35
Indicator
Icon
Event
Priority
Description
Low
General diagnostic message indicator: indicates
that there are diagnostic messages you can
inspect via the DIAGNOSTICS display.
The icon is shut down after you explicitly reset
diagnostics messages either from the display or
via communications (see
Clearing Device
Diagnostics
).
You can disable diagnostic message indicator via
the Display Setup menu (see
Display Setup
).
No Load/Power Flow Direction Indicator
The power flow indicator gives information on the load
presence and shows the direction of active power.
Indicator
Icon
Description
No load.
Direct active power flow – delivered active energy.
Reversed active power flow – received active energy.
Phase Presence Indicators
Phase presence indicators “ABC” show the status of either
Va-Vb-Vc phase-to-neutral voltages in line-to-neutral wiring
modes, or Vab-Vbc-Vca phase-to-phase voltages in line-to-
line wiring modes.
Indicator
Icon
Description
All voltages are present and above the voltage dip threshold.
Blinking phase indicator – the phase voltage is below the
defined voltage dip threshold. Possibly indicates an incorrect
meter nominal voltage setting (see
Basic Meter Setup
in
Chapter 5).
Dashed phase indicator - the phase voltage is either missing or
below the voltage interruption threshold.
If the phase voltage is below the defined voltage dip
threshold, its corresponding phase indicator is blinking.
If the phase voltage is either missing or below the voltage
interruption threshold, the phase indicator is replaced with a
dash.
Display Features
The PowerSmart Socket PQM display has a number of
programmable features that can be disabled, enabled and
adjusted via the meter Display Setup (see
Display Setup
in
Chapter 5).
Backlight
A short press on any button while the display backlight is off
switches the backlight on.
The backlight stays on as long as you selected in the display
setup and then dims to conserve power. The backlight time is
factory set to 1 minute and can be programmed from 1 to 10