Setting-Up Dial-Up GPRS Network

Select Communications Setup from the Meter Setup menu,
and then click on the Dial-Up Networking Setup tab.

The following table lists available connection options.

Parameter

Options

Default

Description

Connection Options

IP Address

192.168.10.203

The IP address on the dial-in
modem PPP network. Not used in
a GPRS network.

Network Subnet
Mask

255.255.0.0

The PPP/GPRS network subnet
mask

Network Default
Gateway

192.168.10.204

The PPP network default gateway.
Not used in a GPRS network.

Redial Attempts

0-1000,

0 = forever

0

The number of dial attempts to
connect to a remote modem if a
connection was unsuccessful.

Connection Timeout

0-9999 sec

120

The modem cancels a call if not
connected within the connection
timeout time.

Time Between Redial
Attempts

0-9999 sec

60

A time delay between redials.

Idle Time Before
Hanging Up

0-9999 sec

0 = never

0

The modem disconnects a call if
idle for more than the specified
idle time.

Rings before Answer 0-99

0 = never

0

The number of rings before the
modem answers an incoming call
from a remote modem. Not used
in a GPRS network.