Setting-up dial-up gprs network – E-Mon E-PS-S-HV-RTU User Manual
Page 68

Chapter 5 Configuring the PowerSmart Socket PQM
Configuring Communications
68
PowerSmart Socket Power Quality Meter
Setting-Up Dial-Up GPRS Network
Select Communications Setup from the Meter Setup menu,
and then click on the Dial-Up Networking Setup tab.
The following table lists available connection options.
Parameter
Options
Default
Description
Connection Options
IP Address
192.168.10.203
The IP address on the dial-in
modem PPP network. Not used in
a GPRS network.
Network Subnet
Mask
255.255.0.0
The PPP/GPRS network subnet
mask
Network Default
Gateway
192.168.10.204
The PPP network default gateway.
Not used in a GPRS network.
Redial Attempts
0-1000,
0 = forever
0
The number of dial attempts to
connect to a remote modem if a
connection was unsuccessful.
Connection Timeout
0-9999 sec
120
The modem cancels a call if not
connected within the connection
timeout time.
Time Between Redial
Attempts
0-9999 sec
60
A time delay between redials.
Idle Time Before
Hanging Up
0-9999 sec
0 = never
0
The modem disconnects a call if
idle for more than the specified
idle time.
Rings before Answer 0-99
0 = never
0
The number of rings before the
modem answers an incoming call
from a remote modem. Not used
in a GPRS network.