Configuring the season tariff and dst schedule – E-Mon E-PS-S-HV-RTU User Manual

Page 107

background image

Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Billing/TOU

PowerSmart Socket Power Quality Meter

107

To configure your daily profiles:

1. Select the desired season and day type.

2. Select the start time for each tariff change point and

the corresponding active tariff number.

3. Repeat the setup for all active profiles.

The first tariff change point is fixed at 00:00 hours, and the
last tariff change you specified will be in use until 00:00
hours on the next day.

NOTE

The billing monthly and daily profile files, and your billing
data display are automatically configured for the number of
active tariffs you defined in the meter TOU daily profile.

Configuring the Season Tariff and DST Schedule

The PowerSmart Socket PQM TOU calendar provides a season
tariff schedule and an option for scheduled daylight savings
switch dates.

To configure your season tariff schedule, select Energy/TOU
from the Meter Setup menu, and then click on the TOU
Calendar tab.

The meter TOU calendar allows you to configure any tariff
schedule based on any possible utility regulation. The
calendar provides 48 entries that allow you to specify profiles
for working days and holidays through all seasons in any
order that is convenient for you, based on simple intuitive
rules. There are no limitations on how to define your
schedule. The meter is able to automatically recognize your