Chapter 5 Configuring the PowerSmart Socket PQM
Configuring the EN50160
PowerSmart Socket Power Quality Meter
129
The default EN50160 compliance limits are shown in the
picture above. You can change the number of the evaluated
harmonics and interharmonics via the
EN50160 Advanced
Setup
.
EN50160 Advanced Setup
The EN50160 Advanced Setup allows you to configure the
EN50160 evaluation options in your meter.
To configure the EN50160 evaluation options:
1. Select Memory/Log from the Meter Setup menu, and
then click on the EN50160 Advanced Setup tab.
2. Change the EN50160 evaluation options if required.
3. Download your setup to the device.
The default EN50160 evaluation options set in your device
are shown in the picture below.
The available options are listed in the following table.
Option
Range
Default
Description
EN50160 Compliance Statistics
Evaluation
Disabled, Enabled Enabled
Enables the EN50160 evaluation
Evaluation Period
Daily, Weekly
Weekly
Defines the EN50160 statistics evaluation
period
First Day of the
Week
Sunday-Saturday Sunday
Defines the first day of the week for
statistics evaluated on a weekly basis
EN50160 Harmonics Survey
Evaluation
Disabled, Enabled Enabled
Enables the harmonics survey log
Evaluation Period
Daily, Weekly
Weekly
Defines the harmonics survey evaluation
period