Chapter 5 Configuring the PowerSmart Socket PQM

Configuring the EN50160

PowerSmart Socket Power Quality Meter

127

Option

Range

Default

Description

PQ Log

Threshold, %

0-200.0%

Defines the operating threshold for a PQ
trigger in percent of the nominal
(reference) value

Hysteresis, %

0-50.0%

5.0

Defines the hysteresis for a PQ trigger in
percent of the threshold

Enabled

Checked

Unchecked

Enables recording PQ events for a specific
voltage characteristic

Waveform Log

On Start

Checked

Unchecked

Checked

Enables waveform log when a PQ event
starts

On End

Checked
Unchecked

Unchecked

Enables waveform log when a PQ event
ends

Log No.

1-2

Specifies the waveform log file used for
waveform recording on a PQ event

Data/RMS trend – Time envelopes and Maximum Durations

Enabled

Checked
Unchecked

Unchecked

Enables recording of the RMS profile during
a fault event

1/2-cyc, cycles

0-1000 cycles

30

Maximum duration of the RMS profile log at
a 1/2-cycle rate.

0.2-s, seconds

0-1000 s

3

Maximum duration of the RMS profile log at
a 0.2-second rate.

3-s, minutes

0-1000 minutes

3

Maximum duration of the RMS profile log at
a 3-second rate.

10-min, hours

0-1000 hours

3

Maximum duration of the RMS profile log at
a 10-minute rate.

Before, Cycles

0-20 cycles

4

The number of cycles to be recorded prior
to the event

After, Cycles

0-20 cycles

4

The number of cycles to be recorded after
the event

Log No.

14

14

Specifies the data log file used for data
recording on the fault event

Waveform log options allow recording waveforms both at the
start and at the end of an event. Since voltage variations can
last from some seconds to minutes, this allows recording
voltage transitions at the beginning and at the end of a
voltage dip or overvoltage using shorter waveforms.

RMS profiling options allow long-duration recording of RMS
voltages and currents while the event continues, using a
variable recording rate and variable averaging intervals.

NOTES

1. The

low

threshold

for

detecting

transient

overvoltages is specified in percent of the nominal
voltage amplitude (1.414 Un), either as a peak value
(from 120%), or as the impulse amplitude (from
20%), depending on the option you selected in the

EN50160 Advanced Setup

.

2. In meters with the fast transient recorder option, the

low threshold for transient overvoltages is limited to
40V. Although you can specify lower values, the
meter will automatically limit it at 40V.

3. With the fast transient recorder, a one-cycle transient

voltage waveform is automatically recorded to
Waveform

log

#3.

If

you

enable

recording