MOD 30ML Multiloop Controller
MODULAR I/O CONNECTIONS
4.4.2 2005A SSR Output (DOM)
Recommended connections to a customer relay are shown in Figure 4-11. Make SSR output
connections as shown in Figure 4-12.
DC output modules are used for controlling or switching DC loads. Each module provides
optical isolation between the field devices and the control logic. This isolation is limited to
250 Vrms at the terminal block. Typical uses and applications for DC output modules include
switching the following loads: DC relays, DC Solenoids, DC motor starters, or DC lamps or
indicators. Wire rating: 600 V, -20°C +105°C UL, CSA approved.
Module Fuse rating: 4 Amps, 250V.
DC DIGITAL OUTPUTS (ISOLATED)
_10_ _11_
Output voltage ranges
5-60 V
5-200 V
Max Output current
1A
0.55A
Turn-off time
0.75 msec
0.75 msec
Max Output voltage drop
1.6 V
1.6 V
Off-state leakage at max V
1 mA
2 mA
AC output modules are used for controlling or switching AC loads. Each module provides
optical isolation between the field devices and the control logic. This isolation is limited to
250 Vrms at the terminal block. Typical uses and applications for AC output modules include
switching the following loads: relays, solenoids and contactors, motor starters, heaters,
lamps, or indicators. Wire rating: 600 V, -20°C +105°C UL, CSA approved. Module Fuse
rating: 4 Amps, 250V.
AC DIGITAL OUTPUTS (ISOLATED)
_12_ _13_ _14_
Output voltage range
12-140 V
24-280 V
24-280 V
Max Output current
1A
1A
1A
Off-state leakage
5 mA
5 mA
5 mA
(2.5 at 120V)
Minimum load current
20 mA
20 mA
20 mA
Response time
1/2 cycle 1/2
cycle 1/2
cycle
Max Output voltage drop
1.6 V
1.6 V
1.6V
Form
A (Make)
A (Make)
B (Break)
Type
SPST-NO SPST-NO SPST-NC
Figure 4-11. Recommended Connection to Solid State Relay