background image

MOD 30ML Multiloop Controller

MODULAR I/O CONNECTIONS

4.4.2 2005A SSR Output (DOM)

Recommended connections to a customer relay are shown in Figure 4-11. Make SSR output
connections as shown in Figure 4-12.

DC output modules are used for controlling or switching DC loads. Each module provides
optical isolation between the field devices and the control logic. This isolation is limited to
250 Vrms at the terminal block. Typical uses and applications for DC output modules include
switching the following loads: DC relays, DC Solenoids, DC motor starters, or DC lamps or
indicators. Wire rating: 600 V, -20°C +105°C UL, CSA approved.
Module Fuse rating: 4 Amps, 250V.

DC DIGITAL OUTPUTS (ISOLATED)

_10_ _11_

Output voltage ranges

5-60 V

5-200 V

Max Output current

1A

0.55A

Turn-off time

0.75 msec

0.75 msec

Max Output voltage drop

1.6 V

1.6 V

Off-state leakage at max V

1 mA

2 mA


AC output modules are used for controlling or switching AC loads. Each module provides
optical isolation between the field devices and the control logic. This isolation is limited to
250 Vrms at the terminal block. Typical uses and applications for AC output modules include
switching the following loads: relays, solenoids and contactors, motor starters, heaters,
lamps, or indicators. Wire rating: 600 V, -20°C +105°C UL, CSA approved. Module Fuse
rating: 4 Amps, 250V.

AC DIGITAL OUTPUTS (ISOLATED)

_12_ _13_ _14_

Output voltage range

12-140 V

24-280 V

24-280 V

Max Output current

1A

1A

1A

Off-state leakage

5 mA

5 mA

5 mA

(2.5 at 120V)
Minimum load current

20 mA

20 mA

20 mA

Response time

1/2 cycle 1/2

cycle 1/2

cycle

Max Output voltage drop

1.6 V

1.6 V

1.6V

Form

A (Make)

A (Make)

B (Break)

Type

SPST-NO SPST-NO SPST-NC

Figure 4-11. Recommended Connection to Solid State Relay