5.3. Resin gel alarm (RGA) – Flush machine!

If during an injection, the pumps do not move a complete stroke in the time specified
in resin alarms configuration screen (see section 4.4), this alarm is generated. This
alarm is designed to prevent the user accidentally allowing resin to gel in the mixing
head, and indicates the pumps have stalled during an injection.

To clear the alarm either flush the machine or adjust machine settings to make the
pumps start pumping once again.

5.4. Autosprue 1 position error

This alarm is produced if a sprue is enabled with limit switch monitoring, but fails to
report the correct position during an injection. To clear the alarm the fault must be
corrected. See Table 5.0 for a list of possible problems and suggested actions to
provide a solution.

This alarm will prevent the operator from starting the machine and stops the machine.

Problem

Suggested solution

Sprue mechanically prevented from
moving between open/closed states

Service auto sprue

Sprue does not change position

Ensure air line is correctly connected

Sprue moves correctly

Are electrical connections connected
correctly/wiring fault

No limit switches in use

Disable limit switch monitoring

Table 5.0 – Possible causes for autosprue position errors and remedies

5.5. Autosprue 2 position error

See section 5.4.

5.6. Autosprue 3 position error

See section 5.4.

5.7. Autosprue 4 position error

See section 5.4.

5.8. Motor comms error

This alarm is displayed if the motors fail to respond to a communications request from
the PLC. If this error occurs, it implies that an equipment failure has occurred and a
suitably trained maintenance technician should be informed.
Acknowledge the fault to clear it.

5.9. Motor fault

This is a general motor fault condition. Ensure the e-stop button is not activated and
safety circuit has been reset. Powering the machine down and then restarting after
waiting for 60 seconds can be tried, if the alarm persists.