44

LCR Troubleshooting Guide

1. Insert a delivery ticket into the Epson printer and start a

delivery.

Foreign debris in system.

2. Move the selector switch from RUN to STOP and back to

RUN

. Listen for an audible clicking sound from the solenoids.

3. If there is an audible click from the solenoid (but still no flow),

this may be an indication of a mechanical problem with the

main valve or its associated components. Contact your local

Liquid Controls Service Center or the Liquid Controls Service

Depar

4. If there is NO audible click from the solenoid, check the

voltage to Pin #s 14, 15, 16 and 17 of terminal block J13.

While still in RUN mode, use a reliable multimeter to measure

the following DC voltages on the circuit board. Use J8 pin

#38 as a groun

TERMINAL # VOLTAGE

J13 #14 12.0VDC ±1.5VDC

J13 #15 1.0VDC ± 0.5VDC

J13 #17 12.0VDC ±1.5VDC

J13 #18 1.0VDC ±0.5VDC

5. If the above voltages are correct, this may be an indication of

a problem with the valve or its associated components.

Contact your local Liquid Controls Service Center or the

Liquid Controls Service Department for assistance.

6. If the above voltage are NOT correct, replace the following

components with known working units until the problem is

resolved:

Solenoids* Varies depending on system.

LCR Circuit Board* Part # 81547-1 for series E3611X and

E3612X

*Contact your local Liquid Controls Service Center or the

Liquid Controls Service Department for assistance.

Valve will not

open.

Solenoids are inactive or

inoperative.

SOLUTION

PROBABLE CAUSE

PROBLEM