Advanced Operations
6.3.3.6 Function set to PWM CONTROL/LINEAR working mode
Table 34 Color/line code for
Error list
Warning list
Process event
Relay contact (SET TRANSFER=ENERGIZED)
Relay contact (SET TRANSFER=DE-ENERGIZED)
PWM CONTROL/LINEAR
SET FUNCTION
Default value: LINEAR
The 2nd SET FUNCTION menu sets the PWM signal status
LINEAR
Signal is linearly dependent on the process value.
PID CONTROL
Signal works as a PID controller.
SET TRANSFER
Default value: 0 seconds
Sets a substitute PWM ratio when some error conditions are detected in the selected source or if
the source is missing.
HIGH ALARM
Default value: 15
Sets the process value which leads the PWM ratio to 100 % (DUTY CYCLE set to DIRECT).
LOW ALARM
Default value: 5
Sets the process value which leads the PWM ratio to 0 % (DUTY CYCLE set to DIRECT).
PERIOD (0 s
–
600 s)
Default value: 5 seconds
Sets the duration time of one PWM period.
MINIMUM
(0 %
–
100 %)
Default value: 0 %
Lower limit of the operation range.
MAXIMUM
(0 %
–
100 %)
Default value: 100 %
Upper limit of the operation range (
).
DUTY CYCLE
Default value: DIRECT
Sets the status of PWM ratio.
DIRECT
PWM ratio rises with a rising process value.
REVERSE
PWM ratio falls with a rising process value.
INPUT VALUE
Displays the process value read from the selected source after it has been processed by the
internal formula parser (if prompted).