Status Page Configuration

You may set defaults for the Status screen here.

1. In “Refresh Rate (seconds),” enter the number of seconds you would like the Status

screen to refresh at. You may enter a value from 1 to 65535. The default is 60 seconds
(i.e., every 1 minute).

2. In “HTTP Port,” you may change the port number your web browser uses to connect to

your Room Alert’s web interface. It uses port 80 by default.

3. In “Temperature Scale,” you may choose “Fahrenheit” or “Celsius” from the drop-down

list. “Fahrenheit” is the default.

4. In “Sensors To Display,” you may choose “All Sensors” or “Only Connected” from the

drop-down list. Selecting “Only Connected” will hide the digital sensor channel if there
is no digital sensor connected to your Room Alert 12E.

5. Click

Accept Changes

at the bottom of your screen to temporarily save your settings.

You may now navigate to another screen; however, if you close the web interface before
the next step, you will lose your changes.

6. Click

Save Settings

in the navigation bar to the left of your screen. Your Room Alert

12E will automatically reboot and commit your changes.

Device ManageR Push Configuration

By default, Device ManageR queries your Room Alert 12E for sensor values at defined intervals.
However, you may configure your Room Alert 12E to proactively send sensor updates to Device
ManageR by enabling “Device ManageR Push.”

Enabling “Device ManageR Push” is an advantage for two reasons:

• Your Room Alert 12E can communicate with Device ManageR without triggering

any firewalls between the two. Firewalls typically allow out-going connections while
blocking in-coming connections.