Room Alert 12E

20

AVTECH Software, Inc.

SNMP Configuration

To begin configuring your Room Alert 12E for SNMP:

1. In “Community Name,” you may leave the default SNMP protocol community name—

“public”—or enter a new name.

2. You may leave “Contact (sysContact)” blank or enter a person’s name to specify who is

receiving the information.

3. You may leave “Location (sysLocation)” blank or enter the location of your Room Alert

12E monitor.

4. You may click

Use 2 digit SNMP

if you prefer to receive values in 2-digit rather than

4-digit format.

5. Click

Accept Changes

at the bottom of your screen to temporarily save your settings.

You may now navigate to another screen; however, if you close the web interface before
the next step, you will lose your changes.

6. Click

Save Settings

in the navigation bar to the left of your screen. Your Room Alert

12E will automatically reboot and commit your changes.

TIP

Room Alert 12E sends values to your 3

rd

-party SNMP

monitoring application in 4-digit format by default. 78.55° F, for
example, appears as 7855. In 2-digit format, your values are
truncated, not rounded to the nearest number. In this example,
78.55 would appear as 78.

TIP

The community name you assign here must match the one in
your 3

rd

-party SNMP monitoring application.