AVTECH Room Alert 12ER Monitor (RA12E-TH1-RAS) User Manual
Page 32
Room Alert 12E
28
AVTECH Software, Inc.
External Switch Sensor Settings 1–4
You may configure the alert state for the four external switch sensors in the “Switch Sensor
Settings” fields. Shown below are the default settings for the four switch sensors.
Your Room Alert 12E monitors your switch sensors for an “Open” or “Closed” circuit state.
Room Alert defaults to alarming on “Closed,” as you can see above; you may, however, need to
change that depending on the type of sensor. AVTECH’s Motion Sensor, for example, is “Open”
when it detects movement and “Closed” when it doesn’t; in that case, you would typically want
to configure the sensor to alarm on “Open” or when motion is detected.
The Alarm And Clear State Of Your Switch Sensor
To determine the alarm and clear state of your sensor, you may either refer to its Installation
Note or see for yourself by physically connecting your sensor to your Room Alert and then
observing what happens to its circuit state in the Status page.
After you connect your sensor and before you configure it in the Settings page, follow these
steps: