AVTECH Smoke Sensor w_Escape Light (RMA-SS1-SEN) User Manual

Smoke sensor w/escape light, Room alert

background image

Smoke Sensor w/Escape Light

Instructions For Installing The Smoke Sensor w/Escape Light

AVTECH Software

Phone 401.628.1600

Sales 888.220.6700

Web AVTECH.com

Application Note

Room Alert

Mount the Smoke Sensor where

desired and run the sensor cable

back to the Room Alert ID Box.

Connect the sensor cable to the

contacts for a single switch sensor.

© 1988 - 2012 AVTECH Software, Inc. All Rights Reserved.

The Screw Connectors On The Sensor ID Boxes Are Volt-Free Contacts Only. Do Not Connect These Terminals To Any Live Circuit.

A Qualified Electrician Should Be Consulted To Test Any Wires You Connect To The Room Alert ID Box For The Presence Of Electrical

Voltages And If Any Are Detected, They Must Not Be Wired To The ID Box. The ID Box May Become Dangerous If You Connect It

To A Live Circuit. Never Connect Main Power To Any Of The Room Alert Sensors Unless Specifically Instructed To Do So Using The

AVTECH Software 5V Power Adapter. If Required, An AVTECH Software 5V Power Adapter Will Be Included With That Sensor.

DO NOT Use Switch Sensors In ‘Explosive’ Environments Unless Approved For Those Environments.

IMPORTANT SAFETY NOTICE

The Smoke Sensor w/Escape Light is a smoke/fire detector with specially designed additional electronics

that allow it to interface to a Room Alert ID Box. It is powered by one 9v Alkaline battery which should

be replaced at least once per year. Please schedule the replacement of batteries on an annual basis to help

guarantee battery reliability. Test the Smoke Sensor initially by pressing its ‘Test’ button. The Smoke Sensor

should also be tested once a month by pressing the ‘Test’ button to ensure that the unit is operational. A very

loud ‘buzzer’ should sound when the test button is pressed.

NOTE: When these sensors are shipped the battery is placed in the battery tray backwards and upside down to prevent

the ‘buzzer’ from engaging during transport. Make sure to remove the battery and place it in the battery tray properly before

continuing with setup.

Carefully mount the Smoke Sensor to the ceiling or wall at a suitable position in the room using the two

mounting holes in the base of the unit. It must be located at least 18 inches from the corners of any walls

and ceilings to avoid smoke ‘dead-spots’.

To connect the Smoke Sensor to the Room Alert ID Box, run the sensor cable back to the Room Alert ID Box and

connect the wire to the contacts for a single switch sensor. There is no polarity associated with the connections on

the ID Box.

Sensor cable can be any low voltage cable such as bell wire, speaker cable, data cable or telephone cable.

Minimum voltage insulation 50v, minimum current carrying capacity 1A. Maximum recommended length is

approximately 100´ although shorter lengths will yield more reliable performance and distances up to 900´ are

possible. Test your setup to ensure proper operation. The Smoke Sensor provided with Room Alert is ‘Volt-Free’.