0 alpha mib parameters, 1 definitions and settings, Parameter oid description access type value – Alpha Technologies AlphaNet IDH4 for XM2 and XM2-300HP Series - Technical Manual User Manual
Page 73
73
746-257-B2-001, Rev. B (01/2014)
10.1 Definitions and Settings
10.0 Alpha MIB Parameters
Parameter
OID
Description
Access Type
Value
GENERAL CONTROLS
atiMgmtSysTamperPolarity
1.3.6.1.4.1.926.1.3.2.6.1.0
Determines when tamper is active
Read/Write
Integer
1=doorOpenWhenContactOpen
2=doorOpenWhenContactClosed
(default)
atiMgmtSysAlphaBusSize
1.3.6.1.4.1.926.1.3.2.6.2.0
Internal microprocessor communications
bus size. Alpha XM2 series power supplies
use 9 bit. Alpha GMX and VMX series
supplies use 8 bit
Read/Write
Integer
1=9 Bit (Default)
2=8 Bit
atiMgmtSysGnrlInfoConfigs
1.3.6.1.4.1.926.1.3.2.7.1
Object Identifier
atiMgmtSysGnrlInfoConfigsMain
1.3.6.1.4.1.926.1.3.2.7.1.1.0 An ASCII string programmed into the main
board non-volatile memory.
Read Only
Octet String
Product number, configuration
number serial number, etc.
atiMgmtSysGnrlInfoConfigsDaughter
1.3.6.1.4.1.926.1.3.2.7.1.2.0 An ASCII string programmed into the C/D
battery circuitry.
Read Only
Octet String
Product number, configuration
number serial number, etc.
atiMgmtSysGnrlInfoConfigsBase
1.3.6.1.4.1.926.1.3.2.7.1.3.0 An ASCII string describing the base
configuration of the device.
Read Only
Octet String
i.e. DSM3, DSM3x, DPM, etc.
ENVIRONMENTAL I/O CONTROLLER
atiMgmtSysIo
1.3.6.1.4.1.926.1.3.2.8
Object Identifier
atiMgmtSysIoSelect
1.3.6.1.4.1.926.1.3.2.8.1
Indicates what function the IO pins are
being used for
Read/Write
Integer
1 = Generic
2 = lapOnly
3 = heaterControlOnly
4 = generatorOnly
5 = heaterControlAndLap
6 = generatorAndLap
atiMgmtSysIoLAPState
1.3.6.1.4.1.926.1.3.2.8.2
Current state of the LAP device
Read Only
Integer
1: notInstalled(1)
2: ok(2)
3: acNotPresent(3)
4: lapBlown(4)
5: lapFail(5)
atiMgmtSysIoGenState
1.3.6.1.4.1.926.1.3.2.8.3
State of the DC Emergency Generator
when sense lines are used
Read Only
Integer
1: notInstalled(1)
2: genOff(2)
3: genRunning(3)
4: genNotDetected(4)
5: error(5)
atiMgmtSysIoPinCtrl
1.3.6.1.4.1.926.1.3.2.8.20
Status of the ENV connector Output Pin
(Pin 3)
Read Only
Integer
1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn4
1.3.6.1.4.1.926.1.3.2.8.21
Status of the ENV connector Input Pin#4
Read Only
Integer
1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn5
1.3.6.1.4.1.926.1.3.2.8.22
Status of the ENV connector Input Pin#5
Read Only
Integer
1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn6
1.3.6.1.4.1.926.1.3.2.8.23
Status of the ENV connector Input Pin#6
Read Only
Integer
1 = Contact Open
2 = Contact Closed
PLATFORMS
atiProductPlatforms
1.3.6.1.4.1.926.1.4
Object Identifier
atiBroadbandUPS
1.3.6.1.4.1.926.1.4.1
Object Identifier
atiBBSysView
1.3.6.1.4.1.926.1.4.1.1
Object Identifier
atiBBSysViewSelects
1.3.6.1.4.1.926.1.4.1.1.1
Object Identifier
atiBBSysViewSelfTestControl
1.3.6.1.4.1.926.1.4.1.1.1.1.0 Starts/Stops a system self-test.
Read/Write
Integer
1=Stop
2=Start
atiBBSysViewSelfTestInhibit
1.3.6.1.4.1.926.1.4.1.1.1.2.0 System self-test is prevented. On reset,
the IDH4 gets this value from the master
XM2 (in a system with more than one
power supply).
Read/Write
Integer
1=Normal (Default)
2=Inhibited
atiBBSysViewSystemControlMgr
1.3.6.1.4.1.926.1.4.1.1.1.3.0 If the System Control Manager is running,
the Small System Controller/Administrator
(SSC or SSA) is running and there is
coordination between the power supplies
for charging, testing, etc. The value of this
item is stored in non-volatile memory.
Read/Write
Integer
1=Running
2=Disabled