beautypg.com

0 start up and verification – Alpha Technologies AlphaNet IDH4 for XM2 and XM2-300HP Series - Technical Manual User Manual

Page 70

background image

70

746-257-B2-001, Rev. B (01/2014)

Configuring the Rx/Tx Power LED - Custom Settings
If desired, the RF Power Level ranges for the Rx/Tx PWR LED may be customized via

SNMP by adjusting the HiHi, Hi, Lo, LoLo values for the docsIfDownChannelPower and

docsIfCmStatusTxPower in the SCTE-HMS Property Table (OID:1.3.6.1.4.1.5591.1.1.1). Be

careful not to exceed the Input Level and Output Power range specifications of the IDH4 Series

transponder.
COM - AlphaBus Communications
The COM LED indicates any data traffic being received by the IDH4 Series through the COM

(AlphaBus) port. This LED will also blink with one to three blinks approximately every 10 seconds,

which indicates communication exists between the IDH4 Series and other connected devices,

such as a generator or additional XM2.
BAT A/B - Battery Strings A & B
The LED indicator remains ON solid when the battery string wiring harness is correctly connected

to the batteries and the Bat A/B connector on the IDH4 and IDH4X Series.
BAT C/D - Battery Strings C & D
The LED indicator remains ON solid when the battery string wiring harness is correctly connected

to the batteries and the Bat C/D connector on the IDH4X.

9.3.2 Resetting the Transponder

Should the need arise to reset the transponder locally, such as in the case of adding additional

power supplies, a generator, or carrying out maintenance activities, do the following:
Press and hold the reset button (RST) for approximately three (3) seconds until the ALM/RDY

LED stops blinking and turns solid (green). Release the button. The transponder will perform its

power up sequence.

9.4

Verifying Communications via the Headend

Using SNMP, check connectivity by verifying power supply data by doing the following:
• With a MIB browser check power supply data in the psIdent MIB branch (1.3.6.1.4.1.5591.1) of the

SCTE-HMS tree.

• With network management software, verify the IDH4 Series has been identified and is reporting data

correctly.

9.3.1 Detailed LED Descriptions

9.0 Start Up and Verification