6.3
The Alpha MIBs
6.3.1 The Alpha MIB Structure
Measurements and settings for the power supply, generator, batteries and IDH4 are accessed
using Simple Network Management Protocol (SNMP) through the Alpha Management Information
Base (MIB) files.
The Alpha MIB is defined within the enterprise branch of the MIB tree starting at 1.3.6.1.4.1.926
and is organized into the following branches:
6.0 Data Management
Refer to Section 10 for further details regarding the Alpha MIBs.
Alpha CIB Tables – atiTables (1.3.6.1.4.1.926.1.2.1)
Power supply, generator, battery and IDH4 data and settings are located in the CIB Tables branch (atiCibTables). The tables are sorted into
the following categories:
1.
Discretes - XM2 major alarms & installed XM2 options.
2.
Analogs - Voltages, currents, frequencies, temperatures.
3.
Counters - Batteries per string, number of strings, XM2 self-test schedule, device address, total run time and configuration settings.
4.
Version - Device version information.
Alpha Management – atiManagement (1.3.6.1.4.1.926.1.3)
Advanced IDH4 settings are located in the Alpha management branch (atiManagement) and the settings are split between SNMP and
system-related settings.
1.
SNMP Management – atiMgntSnmp (1.3.6.1.4.1.926.1.3.1)
SNMP Trap tables, SNMP access, Community Strings and SNMP Trap controls.
1.1
SNMP Trap Table - Table of SNMP trap addresses.
1.2
SNMP Access Table – Table of SNMP access addresses.
1.3
SNMP Access – Device accessibility via SNMPv1 & SNMPv2.
1.4
CPE Mode – Enable/disable dual IP and static IP settings.
1.5
Community Strings – Get, set and trap community strings.
1.6
SNMP Trap controls – Trap on normal, send count, SNMP timeout.
2.
System Management – atiMgmtSys (1.3.6.1.4.1.926.1.3.2)
Download, Web server, SNTP server IP addresses, enclosure environmental controller, and general controls (tamper polarity).
2.1
Download – IDH4 Proprietary Configuration File settings.
2.2
HTTP Access - Enable/disable Web page – IDH4.
2.4
System Servers – Simple Network Time Protocol server (SNTP) IP address.
2.5
Temperature Manager – Battery heater mat or enclosure cooler settings.
2.6
Phone Home – IP address and timer settings.
2.7
General Controls – Tamper switch polarity and internal bus data size.
2.8
General Info – Base configuration of the device. i.e. IDH4x, IDH4L.
2.9
Non-volatile Memory Defaults – Factory and custom defaults.
Alpha Product Platforms – atiProductPlatforms (1.3.6.1.4.1.926.1.4)
System power supply parameters are located the Alpha Product Platforms branch (atiProductPlatforms).
1.
Broadband UPS
System View – Self Test, alarms, scalars, and counters reported by the host device.
1.1
Self Test – Start/stop, prevention and System Control Manager.
1.2
Alarms – Status of major and minor alarm, self test, temperature probe and input power.
1.3
Scalars – Power supply input voltage, frequency and current. Battery voltage and temperature. Charger settings.
1.4
Counters – Self Test and inverter counters.