beautypg.com

2 control connections, 3 fault shutdowns, 1 generator set master switch – Alpha Technologies AlphaGen 3.5_5.0kW Kohler COM5 User Manual

Page 56: 2 remote start/stop connections, 3 status indicators

background image

TP-6482 8/06

56

Section 6 Controller Operation and Test

6.2 Control Connections

Wiring harnesses connect the generator set control
board to the system remote controls and the engine.
Figure 6-2 shows the wiring harness connections to the
control board. See the wiring diagrams in Section 8 for
pinouts and connection details. Figure 6-3 defines the
abbreviations used in the wiring diagrams.

M-337000C-B

1. Generator set to remote control system

interface harness, GM14245

2. Generator set control circuit board
3. Engine interface harness, GM14244

1

3

P1

P2

P3

R37

2

P3

P1

P6

P1

J4

P5

P2

Figure 6-2

Generator Set Control Connections

Abbreviation

Definition

N

Ground

OVC

Overcrank

N/C

Not connected

STT

Start

LOP

Low oil pressure

STP

Stop

OVT

Overtemperature

OVS

Overspeed

DCP

DC output sensing

DCN

DC output sensing

AC1

AC speed sensing

AC2

AC speed sensing

M1

Throttle control

M2

Throttle control

M3

Throttle control

M4

Throttle control

P

Battery

70

Run

71

Crank

Figure 6-3

Pin Abbreviations

6.2.1

Generator Set Master Switch

Some models use a 3-position generator set master
switch. Set the switch to the AUTO position for remote
operation. Set both the generator set master switch and
the remote switch to the STOP or OFF position and
disconnect the engine starting battery before servicing
the generator set.

Other models use a momentary start/stop generator set
switch that returns to the center position when released.
Be sure to set the remote switch to the OFF position
before servicing the generator set. Hold the generator
set master switch in the STOP position while
disconnecting the starting battery.

6.2.2

Remote Start/Stop Connections

For remote operation, connect a three-wire remote
start/stop switch to P6 of the interface harness. To start,
open a contact between pins 6 and 7 and close a contact
between pins 5 and 6 of connector P6 (see the wiring
diagrams). To stop, close the contact between pins 6
and 7 and open the contact between pins 5 and 6.

6.2.3

Status Indicators

Eight LEDs on the generator set control board indicate
the system status conditions and fault shutdowns listed
in Figure 6-4. Figure 6-1 shows the LED locations.

LED

Indicates

Remote

Annunciation

1

Overspeed shutdown

Yes

2

Overtemperature shutdown

Yes

3

Engine running status indicator

Yes

4

Low oil pressure fault shutdown

Yes

5

Overcrank shutdown

Yes

6

Fuel valve energized

No

7

Cranking energized

No

8

Common fault indicator

No

Figure 6-4

Control Board LEDs

6.3 Fault Shutdowns

The generator set shuts down automatically under the
fault conditions listed in Figure 6-5 and cannot be
restarted until the controls are reset. Correct the fault
condition and then reset the controller by placing either
the remote control switch or the generator set master
switch in the STOP position.

The high engine

temperature fault automatically resets when the
generator set cools.

Refer to the troubleshooting charts in Sections 4 to
further diagnose the cause of a fault shutdown.