Section 3 Scheduled Maintenance
M-337000B-B
1
4
5
2
3
1. Oil check, fill
2. Exhaust pipe connection
3. Oil cooler
4. Oil filter
5. Oil drain
Figure 3-5
Lubrication System, Specification Numbers GM14140-GA1 and above
3.4.2
Engine Oil Recommendation
Kohler Co. recommends API (American Petroleum
Institute) Service Class SG, SH, or SJ 5W-30 synthetic
oil. Synthetic oil oxidizes and thickens less than other
oils and leaves fewer deposits on the engine intake
valves and pistons.
3.4.3
Oil Change Procedure
Allow the oil to cool to a safe temperature before
changing.
1. Follow the instructions in Section 3.3 to access the
generator set oil drain plug, filter, and fill tube. See
Figure 3-4 and Figure 3-5.
2. Drain the oil.
a. Place an oil collection container below the oil
drain and remove the oil drain plug.
b. Allow the engine oil to drain completely.
c. Replace the oil drain plug.
3. Replace the oil filter.
a. Place an oil collection container below the oil
filter.
b. Remove
the
oil
filter
by
rotating
it
counterclockwise with an oil filter wrench.
c. Clean the gasket sealing surface of the oil filter
adapter.
d. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
e. Install the new oil filter following the instructions
provided with the filter. Hand-tighten the filter.
Note: Dispose of all waste materials (engine
oil, fuel, filter, etc.) in an environmentally
safe manner.
4. Fill with oil.
a. Remove the oil fill cap and fill the engine to the F
mark on the dipstick. The engine oil capacity is
2.0 L (2.1 qt.).
See Section 3.4.2 for oil
selection.
b. Reinstall the dipstick and the oil fill cap.
5. Slide the generator set back into the cabinet and
reconnect the exhaust pipe and wiring harnesses
as described in Section 3.3. Do not replace the
compartment front panel.