Troubleshooting chart (continued) – Alpha Technologies AlphaGen 3.5_5.0kW Kohler COM5 User Manual
Page 33
![background image](/manuals/317347/33/background.png)
TP-6482 8/06
33
Section 4 General Troubleshooting
Troubleshooting Chart (continued)
Problem
Possible Cause
Corrective Action
Reference
Unit cranks but does not
t t
ti
d
Faulty spark plug
Replace or regap spark plugs.
Section 3.8.2
start, continued
Loose spark plug wire connection
Reconnect and/or tighten spark plug wire.
—
Ignition system problem
Test ignition system. Replace ignition module if
faulty.
Sections 6.5.4
and 5.5
Weak or dead battery
Recharge or replace battery.
Section 3.7
Unit starts hard
Air cleaner clogged
Clean or replace air cleaner element.
Section 3.5
Faulty spark plug
Replace or regap spark plugs.
Section 3.8.2
Weak or intermittent ignition module(s)
Test the ignition system and replace faulty
components.
Section 5.5
Unit stops suddenly
Air cleaner clogged
Clean or replace air cleaner element.
Section 3.5
p
y
Faulty spark plug
Replace or regap spark plugs.
Section 3.8.2
Fuel starvation
Replenish fuel.
—
Engine harness connector not fully locked
tight
Disconnect and reconnect.
—
Fault shutdown
Check controller LEDs. Correct fault and reset
controller. Test shutdown operation.
Sections 6.2.3,
2.3.6 and 6.4
Faulty shutdown switch
Test switches and replace if necessary.
Section 5.9
Unit lacks power or
operates erratically
Engine harness connector not fully locked
tight
Disconnect and reconnect.
—
p
y
Air cleaner clogged
Clean or replace air cleaner element.
Section 3.5
Insufficient cooling
Inspect and clean cooling system.
Section 3.9
Engine overload
Reduce load on generator set.
—
Faulty spark plug
Replace or regap spark plugs.
Section 3.8.2
Fuel supply problem
Check valves and fuel pressure.
Section 5.7
Governor system problem
Check governor and throttle linkage.
Section 5.4
Unit does not supply load
Fuel supply problem
Check for the correct fuel and fuel block
connection.
Section 5.7
Excessive load
Check that load does not exceed rating, 3.5 or
5 kW.
—
Throttle linkage binding
Check that throttle linkage is free to move and
open while engine is running.
Section 5.4
Undervoltage
Check that voltage with no load is 52 volts (48 V
models) or 39 volts (36 V models).
Section 5.3
Engine noise
Hydraulic lifter leakdown
Run unit 5--10 minutes under load.
—
Unit overheats
Air openings clogged
Clean intake and outlet openings.
Section 3.9
Air cleaner clogged
Clean or replace air cleaner element.
Section 3.5
Overload
Verify that load is within the specified range.
Reduce load.
Section 1.3