Troubleshooting chart (continued) – Alpha Technologies AlphaGen 3.5_5.0kW Kohler COM5 User Manual

Page 33

background image

TP-6482 8/06

33

Section 4 General Troubleshooting

Troubleshooting Chart (continued)

Problem

Possible Cause

Corrective Action

Reference

Unit cranks but does not

t t

ti

d

Faulty spark plug

Replace or regap spark plugs.

Section 3.8.2

start, continued

Loose spark plug wire connection

Reconnect and/or tighten spark plug wire.

Ignition system problem

Test ignition system. Replace ignition module if
faulty.

Sections 6.5.4
and 5.5

Weak or dead battery

Recharge or replace battery.

Section 3.7

Unit starts hard

Air cleaner clogged

Clean or replace air cleaner element.

Section 3.5

Faulty spark plug

Replace or regap spark plugs.

Section 3.8.2

Weak or intermittent ignition module(s)

Test the ignition system and replace faulty
components.

Section 5.5

Unit stops suddenly

Air cleaner clogged

Clean or replace air cleaner element.

Section 3.5

p

y

Faulty spark plug

Replace or regap spark plugs.

Section 3.8.2

Fuel starvation

Replenish fuel.

Engine harness connector not fully locked
tight

Disconnect and reconnect.

Fault shutdown

Check controller LEDs. Correct fault and reset
controller. Test shutdown operation.

Sections 6.2.3,
2.3.6 and 6.4

Faulty shutdown switch

Test switches and replace if necessary.

Section 5.9

Unit lacks power or
operates erratically

Engine harness connector not fully locked
tight

Disconnect and reconnect.

p

y

Air cleaner clogged

Clean or replace air cleaner element.

Section 3.5

Insufficient cooling

Inspect and clean cooling system.

Section 3.9

Engine overload

Reduce load on generator set.

Faulty spark plug

Replace or regap spark plugs.

Section 3.8.2

Fuel supply problem

Check valves and fuel pressure.

Section 5.7

Governor system problem

Check governor and throttle linkage.

Section 5.4

Unit does not supply load

Fuel supply problem

Check for the correct fuel and fuel block
connection.

Section 5.7

Excessive load

Check that load does not exceed rating, 3.5 or
5 kW.

Throttle linkage binding

Check that throttle linkage is free to move and
open while engine is running.

Section 5.4

Undervoltage

Check that voltage with no load is 52 volts (48 V
models) or 39 volts (36 V models).

Section 5.3

Engine noise

Hydraulic lifter leakdown

Run unit 5--10 minutes under load.

Unit overheats

Air openings clogged

Clean intake and outlet openings.

Section 3.9

Air cleaner clogged

Clean or replace air cleaner element.

Section 3.5

Overload

Verify that load is within the specified range.
Reduce load.

Section 1.3