Section 4 General Troubleshooting

No

No

Is air cleaner

plugged?

Unit Stops After Normal Operation

Yes

Clean/replace

air cleaner

elements.

Is controller

fault LED lit?

Correct the fault and reset

the controller.

Are fuel solenoid
and wiring okay?

Is fuel adjustment

correct? See Section

5.7.4.

No

Repair/replace

fuel solenoid

and/or wiring.

Are spark plug and

wires okay?

Replace or regap spark

plugs. See Section 3.8.2.

E

Adjust the fuel

metering

valve.*

Possible intermittent wiring

problem or control board

malfunction. Check all

wiring and components.

Yes

No

Yes

* Adjusting the fuel system may void the emissions certification. Only trained and authorized service technicians should

adjust the fuel system. Use the test equipment specified in the test procedure in Section 5.7.4.

Start the unit. Does it stop

after normal operation?

Yes

No

Yes

No

Done.

Are alternator output leads

connected to AC terminals

on the rectifier?

Connect/repair/replace

alternator output leads.

No

Yes