TP-6482 8/06

55

Section 6 Controller Operation and Test

Section 6 Controller Operation and Test

This section describes troubleshooting procedures for
the generator set control board, shown in Figure 6-1.
Refer to the operation manual for operating instructions.
Refer

to

the

remote

controller

manufacturer’s

instructions for troubleshooting and servicing remote
controllers connected to the generator set.

Control circuit boards GM11783 and GM14243 are not
interchangeable.

However, control circuit board

GM17820 can be used to replace either GM11783 or
GM14243.

6.1 Sequence of Operation

The following sections describe the controller sequence
of operation during generator start, run, stop, and fault
shutdown modes.

Use this as a starting point for

controller fault identification.

Use the LEDs on the

controller circuit board to assist in the troubleshooting
process. Refer to the wiring diagrams in Section 8 to
assist in the troubleshooting procedure.

6.1.1

Starting Sequence

Placing the generator set master switch in the RUN
position starts the generator set locally.

With the

generator set master switch in the AUTO position,
momentarily closing contacts P6-5 and P6-6 starts the
generator set remotely.

The crank relay energizes, activating the starter motor,
SM. The hourmeter, ignition module, coil, and gas valve
receive power.

When the engine comes up to speed, the low oil
pressure switch contacts open.

6.1.2

Running Sequence

Leads AC1 and AC2 from the AC side of the voltage
rectifier provide speed sensing signals to the control
board.

Note: The generator set shuts down if the controller

does not obtain AC output within 1 second after
engine start (locked rotor shutdown).

6.1.3

Stopping Sequence

Moving the generator set master switch to the stop
position or closing a remote contact between pins P6-6
and P6-7 (and opening P6-5 and P6-6) deenergizes the
run relay and stops the generator set.

M-337000C-B

1

4

5