Alpha Technologies AlphaGen 3.5_5.0kW Kohler COM5 User Manual

Page 37

background image

TP-6482 8/06

37

Section 4 General Troubleshooting

Is any

controller

fault LED

lit?

Yes

Correct fault

and resume

troubleshooting.

No

Have fuel supply

installer purge air.

Are spark plug wire

connections okay?

Reconnect and/or

tighten.

Does the battery lose

charge while the

system is running?

Check the battery charging

system.

No

Is air cleaner

plugged?

Possible generator set

overload. Does reducing

load solve problem?

(Open circuit breaker to

reduce load.)

Clean or replace air

cleaner elements.

Yes

Reduce the load to keep

it within the rated range.

Lacks Power or Runs Erratically

No

Yes

No

Are spark plugs okay?

See Section 3.8.2.

Regap or replace.

Yes

Go to

D

C

Is fuel

pressure 7-11

in. water?

Yes

Have fuel supply installer

correct fuel pressure

problem.

Ensure that the

main connector is
tightly connected.

Yes

No

No

Yes

No

No

Yes

Has air

been purged

from fuel

lines?