Section 4 General Troubleshooting

4.2 Generator Set/Controller System Troubleshooting Flowcharts

Does

engine
crank?

Does

engine

start?

Yes

No

Did a fault

shutdown

occur?

Is the battery

connected?

No

No

Yes

No

Correct fault, reset

controller, and

continue

troubleshooting from

top of page.

Yes

Yes

Charge or replace the
battery and attempt to
restart. If engine does

not crank, continue

troubleshooting

sequence.

No

Check the battery

voltage. Is battery

fully charged?

Repair/replace starter.

See the Engine Service

Manual.

Yes

Check wiring

harnesses and

connections.

Reconnect, repair, or

replace wiring if

loose or damaged.

Move master switch

to RUN position.

Does engine start

and run normally?

No

Yes

Unit is okay.

Go to

B

Check starter wiring, relay, and

motor. Check voltage to starter

relay on lead 71. See Section

5.6. Is the starter okay?

Replace

controller

board.

Yes

No

Does unit stop

while master

switch is still in

AUTO?

No

Yes

Generator set is okay. The system
may have been sent a remote stop

command, or there may be a

problem with the remote control

system. Refer to the instructions

for the remote control system.

Unplug cabinet interface

connector (P6) to disconnect

remote control system.

Move master switch to

RUN position.

Move master switch
to the OFF position.

Connect the

battery.

Go to

A

Move master switch to STOP

position to reset controller faults.