Appendix i (cont'd.) – Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual
Page 52

52
Appendix I (cont'd.)
Function
Modbus
Code
Point #
Point Description
Range/Value
Address
Unit
04
19
System KW
0 to Span (in Technologic User Setup Menu)
30019
KW
04
20
KW #1
0 to Span (in Technologic User Setup Menu)
30020
KW
04
21
KW #2
0 to Span (in Technologic User Setup Menu)
30021
KW
04
22
KW #3
0 to Span (in Technologic User Setup Menu)
30022
KW
04
23
KW #4
0 to Span (in Technologic User Setup Menu)
30023
KW
04
24
KW #5
0 to Span (in Technologic User Setup Menu)
30024
KW
04
25
KW #6
0 to Span (in Technologic User Setup Menu)
30025
KW
04
26
System Differential Pressure
0 to Span (in Technologic User Setup Menu)
30026
PSI
04
27
System Supply Temperature
0 to Span (in Technologic User Setup Menu)
30027
F°
04
28
System Return Temperature
0 to Span (in Technologic User Setup Menu)
30028
F°
04, 06
29
Setpoint #1
0 to Span (in Technologic User Setup Menu)
30029, 40029
04, 06
30
Setpoint #2
0 to Span (in Technologic User Setup Menu)
30030, 40030
04, 06
31
Setpoint #3
0 to Span (in Technologic User Setup Menu)
30031, 40031
04, 06
32
Setpoint #4
0 to Span (in Technologic User Setup Menu)
30032, 40032
04, 06
33
Setpoint #5
0 to Span (in Technologic User Setup Menu)
30033, 40033
04, 06
34
Setpoint #6
0 to Span (in Technologic User Setup Menu)
30034, 40034
04, 06
35
Setpoint #7
0 to Span (in Technologic User Setup Menu)
30035, 40035
04, 06
36
Setpoint #8
0 to Span (in Technologic User Setup Menu)
30036, 40036
04, 06
37
Setpoint #9
0 to Span (in Technologic User Setup Menu)
30037, 40037
04, 06
38
Setpoint #10
0 to Span (in Technologic User Setup Menu)
30038, 40038
04, 06
39
Setpoint #11
0 to Span (in Technologic User Setup Menu)
30039, 40039
04, 06
40
Setpoint #12
0 to Span (in Technologic User Setup Menu)
30040, 40040
04, 06
41
Setpoint #13
0 to Span (in Technologic User Setup Menu)
30041, 40041
04, 06
42
Setpoint #14
0 to Span (in Technologic User Setup Menu)
30042, 40042
04, 06
43
Setpoint #15
0 to Span (in Technologic User Setup Menu)
30043, 40043
04, 06
44
Setpoint #16
0 to Span (in Technologic User Setup Menu)
30044, 40044
04
45
Pump #1 Speed
0 to 100
30045
%
04
46
Pump #2 Speed
0 to 100
30046
%
04
47
Pump #3 Speed
0 to 100
30047
%
04
48
Pump #4 Speed
0 to 100
30048
%
04
49
Pump #5 Speed
0 to 100
30049
%
04
50
Pump #6 Speed
0 to 100
30050
%
04
51
Lead Pump Number
1 to Pump # (in Technologic User Setup Menu)
30051
04
52
Active Zone Number
1 to Zone # (in Technologic User Setup Menu)
30052
04
53
System Operation Mode
0=Manual, 1=Auto, 2=Auto Bypass, 3=Manual Bypass
30053
04
54
Bypass Valve Position
0 to 100 (0 = Closed, 100 = Open)
30054
04
55
Chiller #1 Flow
0 to Span (in Technologic User Setup Menu)
30055
04
56
Chiller #2 Flow
0 to Span (in Technologic User Setup Menu)
30056
04
57
Chiller #3 Flow
0 to Span (in Technologic User Setup Menu)
30057
04
58
Chiller #4 Flow
0 to Span (in Technologic User Setup Menu)
30058
04
59
Chiller #5 Flow
0 to Span (in Technologic User Setup Menu)
30059
04
60
Chiller #6 Flow
0 to Span (in Technologic User Setup Menu)
30060
04
61
Chiller #1 DP
0 to Span (in Technologic User Setup Menu)
30061
04
62
Chiller #2 DP
0 to Span (in Technologic User Setup Menu)
30062
04
63
Chiller #3 DP
0 to Span (in Technologic User Setup Menu)
30063
04
64
Chiller #4 DP
0 to Span (in Technologic User Setup Menu)
30064
04
65
Chiller #5 DP
0 to Span (in Technologic User Setup Menu)
30065
04
66
Chiller #6 DP
0 to Span (in Technologic User Setup Menu)
30066