4.1.12

Sensor Setup Exit (not PV)

If NO/0 was selected in section 4.1.8 (the sensor

does not provide a PV), the display will show:

Sensor No ## (Type)

Span= # Zero= #

Ok? (Y/N)

If correct, record your sensor setup information on

the wiring diagram that was included with the unit.
Press YES/7 and then ENTER to accept all of the
values shown and return to section 4.1.4.

Press NO/0 and ENTER to return to section 4.1.5 and
modify the sensor.

4.1.13

Copy Sensor

If 2-Copy was selected in section 4.1.2, the display

will show:

Copy to Sensor No: #

From Sensor No: #

Copy? (Y/N)
Exit? (Y/N)

The Copy to Sensor No refers to the sensor number

for which the setup is being performed. The

From

Sensor No

refers to the sensor from which the infor

-

mation will be copied.

Select NO/0 and ENTER, in the

Exit field, to modify

the variables. In the

From Sensor No field, enter the

numeric value of the sensor from which you want to
copy. In the

Copy field, press YES/7 and ENTER to

confirm copying. In the Exit field, press YES/7 and
ENTER to exit. Proceed with section 4.1.11 if the
sensor will provide a PV, and proceed to section
4.1.12 if the sensor will not provide a PV.

4.1.14

Chiller Sensor Span

If 9 = Chi Flow or 10 = Chi DP was selected for the

sensor type in section 4.1.5, then the display will
show:

Sensor No ## (Type)

Span = #####

The span is the sensor value that corresponds to a

20mA signal. Obtain the span of the sensor from the
nameplate on the sensor. Enter the span by pressing
the appropriate numeric keys followed by the ENTER
key.

4.1.15

Chiller Sensor Zero

The display will show:

Sensor No ## (Type)

Span = ##### Zero = #####

The zero is the sensor value that corresponds to a

4mA signal. Typically the variable value is zero at
4mA for many sensors. An exception would be for a
temperature sensor. Enter the desired zero value by
pressing the appropriate numeric keys followed by
the ENTER key.

4.1.16

Chiller Number

The display will show:

Enter the Chiller

No ##

OK ? (Y/N)

Press NO/0 and ENTER to edit the chiller number.

Press the numeric key and ENTER for the chiller you
wish to set up. The chiller number is limited to the
maximum number of chillers allowed, typically 9.
Press YES/7 and ENTER keys to proceed with the set
up.

4.1.17

Chiller Sensor Exit

The display will now show:

Sensor No ## (Type)

Span = ##### Zero = #####
Chill No. #

Ok ? (Y/N)

If correct, record your chiller setup information on the

wiring diagram that was included with the unit. Press
YES/7 and ENTER to accept the values and return to
section 4.1.4.

Press NO/0 and ENTER to return to section 4.1.5 to
modify the sensor.

4.2

Pump Setup Menu

From the Setup Selection Menu, shown in section 4,

Press SETPOINT/2 and ENTER to get to the Pump
Setup Menu shown below. Record your pump setup
information on the wiring diagram that was included
with the unit.

Selection: # 0 = Exit

1 = Enable/Disable
2 = Pump Off Delay
3 = Lag Pump Run Timer

To view the neighboring screen, press the NEXT

SCREEN key. The following will be displayed:

Selection: # 0 = Exit

4 = Hi Load Transfer
5 = Lo Load Transfer

Push the desired numeric key and ENTER to proceed.

4.2.1

Enable/Disable

From the Pump Setup Menu, shown in section 4.2,

Press PROCESS VARIABLE/1 and ENTER to get to
the Enable/Disable screen shown below.

# PUMPS = #

P1: *

P2: *

P3: *

P4: *

P5: *

P6: *
OK ? (Y/N)

*The pump status will be displayed for each defined

pump. Table 3, on the next page, shows the possible
pump states.