Appendix f (cont'd.) – Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual
Page 41

41
Appendix F (cont'd.)
Object Identifier
Object Name
Object Type
Present Value/Range
Binary Input, 59
AI #9 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 60
AI #10 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 61
AI #11 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 62
AI #12 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 63
AI #13 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 64
AI #14 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 65
AI #15 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 66
AI #16 Failure
BINARY_INPUT
1 = Failure 0 = O.K.
Binary Input, 67
Isolation Valve #1
BINARY_INPUT
1 = Open 0 = Closed
Binary Input, 68
Isolation Valve #2
BINARY_INPUT
1 = Open 0 = Closed
Binary Input, 69
Isolation Valve #3
BINARY_INPUT
1 = Open 0 = Closed
Binary Input, 70
Isolation Valve #4
BINARY_INPUT
1 = Open 0 = Closed
Binary Input, 71
Isolation Valve #5
BINARY_INPUT
1 = Open 0 = Closed
Binary Input, 72
Isolation Valve #6
BINARY_INPUT
1 = Open 0 = Closed
Binary Input, 73
Request to Stage Chiller
BINARY_INPUT
1 = Yes 0 = No
Binary Input, 74
Request to De-stage Chiller
BINARY_INPUT
1 = Yes 0 = No
Binary Input, 75
General Alarm
BINARY_INPUT
1 = Alarm 0 = O.K.
Binary Output, 1
Pump Sequence Alternation
BINARY_OUTPUT
1 = Yes 0 = No
Binary Output, 2
System Reset Request
BINARY_OUTPUT
1 = Yes 0 = No
Binary Output, 3
System Start / Stop
BINARY_OUTPUT
1 = Start 0 = Stop
Analog Value, 1
Process Variable #1
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 2
Process Variable #2
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 3
Process Variable #3
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 4
Process Variable #4
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 5
Process Variable #5
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 6
Process Variable #6
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 7
Process Variable #7
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 8
Process Variable #8
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 9
Process Variable #9
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 10
Process Variable #10
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 11
Process Variable #11
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 12
Process Variable #12
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 13
Process Variable #13
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 14
Process Variable #14
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 15
Process Variable #15
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 16
Process Variable #16
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 17
System Flow
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 18
Reserved
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 19
System KW
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 20
KW #1
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 21
KW #2
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 22
KW #3
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 23
KW #4
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 24
KW #5
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 25
KW #6
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 26
Sys Diff Pressure
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 27
Sys Supply Temp
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 28
Sys Return Temp
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 29
Setpoint #1
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 30
Setpoint #2
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 31
Setpoint #3
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 32
Setpoint #4
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)
Analog Value, 33
Setpoint #5
ANALOG_VALUE
0 to Span (in Technologic User Setup Menu)