6.10

Field Repair

General - typical field repair should include: replac

-

ing fuses, replacing input/output modules and assur-
ing connections are correct and secure.

6.11

Program Updating

Contact your Bell & Gossett representative for the

preferred method of upgrading your software.

6.12

Controller Information Screen

To check the program type, scheme, or version num

-

bers, press the F3/8 key while in the Technologic
Pump Controller screen shown in section 3.2. The
screen will now display the Controller Information
Screen shown below.

SYS INFO CPU V: #.##

AS V: #.#.## OS V: #.##

Prog Type: #### ###

Scheme Set #

Press the CLEAR key to exit this screen. If the

factory is called for information or service on this unit,
this information may be requested.

6.13

Logging

Press the F1/5 key, while in the Technologic Variable

Primary Pump Controller screen, to get to the
Logging Menu shown below.

Selection: # Exit = 0

1 = Alarm Log
2 = Pump Log
3 = Data Log

Select the log to view, and press ENTER. Press

PREV. SCREEN or NEXT SCREEN to view more
options on the neighboring screen shown below.

Selection: # Exit = 0

4 = Operation Log
5 = Power Log
6 = Service Log

6.13.1

Alarm Log

From the Logging Menu, shown in section 6.13, press

PROCESS VARIABLE/1 and ENTER to get to the
Alarm Log screen shown below.

DATE

TIME

ALARM

MMDD

HHMM

"

"

"

"

"

"

"

The four digit date is displayed in the MMDD format.

The four digit time is displayed in the 24 hour HHMM
format. Press the CLEAR key to exit this screen.

6.13.2

Pump Log

From the Logging Menu, shown in section 6.13,

press SET POINT/2 and ENTER to get to the Pump
Log Menu shown below.

View Selection #

1 = Pump Run Time.
2 = Pump On/Off Time
0 = Exit

Select the pump log to view.

6.13.2.1

Pump Run Time Log

From the Pump Log Menu, shown in section 6.13.2,

press PROCESS VARIABLE/1 and ENTER to get to
the Pump Run Time Log screen shown below.

Pump Run Time

P1: # P2: #
P3: # P4: #
P5: # P6: #

The pump run time is displayed in total accumulated

elapsed time in hours. Press the CLEAR key to exit
this screen.

6.13.2.2

Pump On/Off Log

From the Pump Log Menu, shown in section 6.13.2,

press SET POINT/2 and ENTER to get to the Pump
On/Off Log screen shown below.

Pump On/Off

P1: # P2: #
P3: # P4: #
P5: # P6: #

The pump on/off times are displayed in total accumu

-

lated times the pumps are switched on and off. Press
the CLEAR key to exit this screen.

DANGER: Troubleshooting live control panels exposes

personnel to hazardous voltages. Electrical trouble-

shooting must only be done by a qualified electrician.

FAILURE TO FOLLOW THESE INSTRUCTIONS WILL

RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.