Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual
Page 33

33
6.10
Field Repair
General - typical field repair should include: replac
-
ing fuses, replacing input/output modules and assur-
ing connections are correct and secure.
6.11
Program Updating
Contact your Bell & Gossett representative for the
preferred method of upgrading your software.
6.12
Controller Information Screen
To check the program type, scheme, or version num
-
bers, press the F3/8 key while in the Technologic
Pump Controller screen shown in section 3.2. The
screen will now display the Controller Information
Screen shown below.
SYS INFO CPU V: #.##
AS V: #.#.## OS V: #.##
Prog Type: #### ###
Scheme Set #
Press the CLEAR key to exit this screen. If the
factory is called for information or service on this unit,
this information may be requested.
6.13
Logging
Press the F1/5 key, while in the Technologic Variable
Primary Pump Controller screen, to get to the
Logging Menu shown below.
Selection: # Exit = 0
1 = Alarm Log
2 = Pump Log
3 = Data Log
Select the log to view, and press ENTER. Press
PREV. SCREEN or NEXT SCREEN to view more
options on the neighboring screen shown below.
Selection: # Exit = 0
4 = Operation Log
5 = Power Log
6 = Service Log
6.13.1
Alarm Log
From the Logging Menu, shown in section 6.13, press
PROCESS VARIABLE/1 and ENTER to get to the
Alarm Log screen shown below.
DATE
TIME
ALARM
MMDD
HHMM
"
"
"
"
"
"
"
The four digit date is displayed in the MMDD format.
The four digit time is displayed in the 24 hour HHMM
format. Press the CLEAR key to exit this screen.
6.13.2
Pump Log
From the Logging Menu, shown in section 6.13,
press SET POINT/2 and ENTER to get to the Pump
Log Menu shown below.
View Selection #
1 = Pump Run Time.
2 = Pump On/Off Time
0 = Exit
Select the pump log to view.
6.13.2.1
Pump Run Time Log
From the Pump Log Menu, shown in section 6.13.2,
press PROCESS VARIABLE/1 and ENTER to get to
the Pump Run Time Log screen shown below.
Pump Run Time
P1: # P2: #
P3: # P4: #
P5: # P6: #
The pump run time is displayed in total accumulated
elapsed time in hours. Press the CLEAR key to exit
this screen.
6.13.2.2
Pump On/Off Log
From the Pump Log Menu, shown in section 6.13.2,
press SET POINT/2 and ENTER to get to the Pump
On/Off Log screen shown below.
Pump On/Off
P1: # P2: #
P3: # P4: #
P5: # P6: #
The pump on/off times are displayed in total accumu
-
lated times the pumps are switched on and off. Press
the CLEAR key to exit this screen.
DANGER: Troubleshooting live control panels exposes
personnel to hazardous voltages. Electrical trouble-
shooting must only be done by a qualified electrician.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL
RESULT IN SERIOUS PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.