beautypg.com

Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual

Page 26

background image

26

Press the numeric key for the chiller you wish to
setup. The chiller number is limited to the maximum
number of chillers. Press ENTER to proceed with the
setup. The display will show:

Chiller # #

Enable/Disable: #

1 = Enable 0 = Disable

Press PROCESS VARIABLE/1 and ENTER if the chiller

will be enabled. If the Chiller is enabled, then the
controller will go to the Chiller Setup screen shown
immediately below.

Press NO/0 and ENTER if the chiller will be disabled.
If the chiller is disabled, then the controller will skip
the following Chiller Setup screen.

Chiller # #

DP Max ## Min # Or

Flow Max # Min #

Ok ? (Y/N)

To accept the values shown and proceed, press

YES/7 and ENTER. To edit the fields, press NO/0
and ENTER. Table 29 gives a description of the Chiller
Setup variables.

Now the display will show:

Do Another ? (Y/N)

Press YES/7 and ENTER to set up another chiller.

Press NO/0 and ENTER to return to the Enbl/Disbl
Chiller screen shown at the beginning of this section.

4.6.2

Chiller's Run Tmr

From the Chiller Setup Menu, shown in section 4.6,

press SET POINT/2 and ENTER to get to the Chiller
Run Timer screen shown below.

Chiller Minimum

Run Timer ### min

Ok ? (Y/N)

To return to the Chiller Setup Menu, shown in section

4.6, press YES/7 and ENTER. To edit the chiller mini-
mum run timer, press NO/7 and ENTER. See Table
30 for a description of the Run Timer.

4.6.3

Isolation Valve

From the Chiller Setup Menu, shown in section 4.6,

press SETUP/3 and ENTER to get to the Chiller
Isolation Valve screen shown below.

Monitor Valve ? (Y/N)

Control Valve ? (Y/N)

Vlv Close Delay ? (Y/N) s

OK ? (Y/N)

To return to the Chiller Setup Menu, shown in section

4.6, press YES/7 and ENTER. To edit the chiller iso-
lation valve, press NO/7 and ENTER. See Table 31
on next page for a description of the Isolation Valve
variables.

Variable

Unit

Description

Default Value

Range

Field Value

DP Max

PSID

Maximum Differential Pressure prior to requesting to

18

0-999

stage another chiller.

DP Min

PSID

Minimum Differential Pressure to be maintained for the

5

0-999

selected chiller.

Flow Max

GPM

Maximum Flow prior to requesting to stage another

0

0-9999

chiller

Flow Min

GPM

Minimum Flow to be maintained for the selected

0

0-9999

enable chiller

Table 29: Chiller Setup Variables

Variable

Unit

Description

Default Value

Range

Field Value

Run

min

Request to destage chiller will not occur until chiller's

10

0-999

Timer

minimum run timer has expired

Table 30: Chiller Run TMr Variable

Variable

Description

Default Value

Range

Field Value

Monitor Valve

A DI signal is supplied from the limit switch on the valve.

N

Y or N

When the switch is closed, the valve is open. If Y is
selected, the pumps will not be allowed to start if all of
the isolation valves are closed.

Control Valve

A DO signal is supplied to control the actuator on the

N

Y or N

isolation valve. When the output is closed, the valve is
to open. Note: the isolation valve must be monitored
if it is controlled.

Vlv Close Delay

Timer to delay closing the isolation valve after stopping

5

0-999

the chiller. This variable is only used for dedicated pump
to chiller systems.

Table 31: Isolation Valve Variables