Press NO/0 and ENTER to edit the fields. To return
to the Stage/Destage Menu, shown in section 4.3.1,
press YES/7 and ENTER. See Table 8 below for a
description of the PV Stage variables.

4.3.1.2

PV Destage

From the Stage/Destage Menu, shown in section

4.3.1, press SET POINT/2 and ENTER to get to the
PV Destage screen shown below.

Destage: ##%

Destg Pr Timer: ##s
HD Spd: ##%
HD Pr Tm: ##s Ok ? (Y/N)

To edit the fields, press NO/0 and ENTER. To return

to the Stage/Destage Menu, shown in section 4.3.1,
press YES/7 and ENTER. See Table 9 below for a
description of the PV Destage variables.

4.3.1.3

EOC Stage

From the Stage/Destage Menu, shown in section

4.3.1, press SETUP/3 and ENTER to get to the EOC
Stage screen shown below.

Pump Max Flow: #

Stage Proof Tm: ##s
Flow Offset: #

Ok ? (Y/N)

To edit the fields, press NO/0 and ENTER. To return

to the Stage/Destage Menu, shown in section 4.3.1,
press YES/7 and ENTER. See Table 10 below for a
description of the EOC Stage variables.

Variable

Unit

Description

Default Value

Range

Field Value

Destage

%

Percentage of the stabilized speed at which the lag pump

85

0-100

will stop

Destg

s

Proof timer prior to stopping lag pump

30

0-999

Pr Timer
HD Spd

%

Lowest speed at which parallel pumps will operate prior

50

0-100

to destaging the lag pump

HD Pr Tm

s

Proof timer prior to destaging the lag pump when

30

0-999

operating below the HD speed

Table 9: PV

Destage Variables

Variable

Unit

Description

Default Value

Range

Field Value

Pump

GPM

Maximum flow allowable prior to starting a lag pump

0

0-9999

Max Flow
Stg Proof

s

Proof timer prior to end of curve staging

30

0-999

Tm
Flow

GPM

Flow rate of constant speed pump supplying variable

0

0-999

offset

speed pump; input only required on series pumping
applications. The flow rate of the constant speed pump is
deducted from the total system flow rate in order to pro-
vide end of curve protection for the variable speed pump

Table 10: PV

EOC Stage Variables

Variable

Unit

Description

Default Value

Range

Field Value

Stg Spd

%

Maximum speed at which the lead pump will operate

95

0-100

prior to starting a lag pump

Stg Proof

s

Proof timer prior to starting lag pump

30

0-999

Timer
Stab

s

Staging stabilization time, delay prior to calculating

60

0-999

Timer

destage value

Table 8: PV

Stage Variables