Page 31

background image

31

5.9

Alternation

From the Technologic Pump Controller screen, shown

in section 3.2, press Alternation/4 to get to the Alter-
nation screen shown below.

Alternate ? (Y/N)

Press YES/7 and ENTER to alternate the sequence

of pump staging. The pump sequence is shown in
the Active Values Seq screen shown in section 5.1.9.
Press NO/0 and ENTER to return to the Technologic
Pump Controller screen without alternating.

Note: Alternation can also be accomplished automat

-

ically. See section 4.3.4.

5.10

Alarms

When the controller detects an alarm condition, the

display will flash *ALARM* in the lower left corner of
the main screen.

The green LED on the HELP key will also flash during
an alarm condition. Press the HELP key for addi-
tional information on the alarm(s). If there are more
than one alarm the alarms will be listed in order of
occurrence.

To view possible causes for alarms press the HELP
key again after the alarm is displayed.

Refer to table Table 35 below for an overview of the
possible alarms and their respective causes.

Press the CLEAR key to return to the main screen.
Pressing RESET may be required to re-start the
system.

The controller logs alarms as they occur to aid in
troubleshooting unobserved alarms. Refer to Section
5.13 for alarm logging information.

HELP

HELP/HELP DETAILED

DESCRIPTION

SCREEN

SCREEN DISPLAY

ALARM

AFD failure

Check H-O-A switch,

The controller is not receiving a closed run signal from AFD number X after it

wiring, and AFDs LED

has been given a start command

Battery Empty

Check battery's voltage

Check for less then a 3V charge on the battery, check battery connection

and its continuity

High Level

Check setting of level

Check for open or closed contacts, refer to wire diagram for proper connection

switch

Low Level

Check setting of level

Check for open or closed contacts, refer to wire diagram for proper connection

switch

Overload Fail

Check amp draw, Use

On Systems with Bell & Gossett bypasses the controller is not receiving a

manual reset if it's OK

digital input from the pump number X starter confirming that it has closed

Pump Fail

Check DP switch,

The controller is receiving a closed signal from the differential pressure switch

impeller, coupler, motor

for pump number X after it has been given a start command

Sensor Fail

Check wiring, piping,

The controller is not receiving the proper 4-20mA signal from zone number

polarity, continuity

X transmitter

Iso Vlv Fail

Check wiring, continuity

This alarm is only available if “Monitor Valve” or “Control Valve” is set to “Y”
in section 4.6.3. The controller will not start the corresponding pump if its
isolation valve is closed. In ganged pump systems, only one isolation valve
needs to be open to run the pumps.

Table 35: Alarm Messages