Appendix F (cont'd.)

Object Identifier

Object Name

Object Type

Present Value/Range

Analog Value, 34

Setpoint #6

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 35

Setpoint #7

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 36

Setpoint #8

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 37

Setpoint #9

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 38

Setpoint #10

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 39

Setpoint #11

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 40

Setpoint #12

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 41

Setpoint #13

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 42

Setpoint #14

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 43

Setpoint #15

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 44

Setpoint #16

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 45

Pump # 1 Speed

ANALOG_VALUE

0 to 100

Analog Value, 46

Pump # 2 Speed

ANALOG_VALUE

0 to 100

Analog Value, 47

Pump # 3 Speed

ANALOG_VALUE

0 to 100

Analog Value, 48

Pump # 4 Speed

ANALOG_VALUE

0 to 100

Analog Value, 49

Pump # 5 Speed

ANALOG_VALUE

0 to 100

Analog Value, 50

Pump # 6 Speed

ANALOG_VALUE

0 to 100

Analog Value, 51

Lead Pump Number

ANALOG_VALUE

1 to Pump # (in Technologic User Setup Menu)

Analog Value, 52

Active Zone Number

ANALOG_VALUE

1 to Zone # (in Technologic User Setup Menu)

Analog Value, 53

Operation Mode

ANALOG_VALUE

0=Manual, 1=Auto, 2=Auto Bypass, 3=Manual Bypass

Analog Value, 54

Bypass Valve Position

ANALOG_VALUE

0 to 100. (0 = Closed 100 = Open)

Analog Value, 55

Chiller #1 Flow

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 56

Chiller #2 Flow

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 57

Chiller #3 Flow

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 58

Chiller #4 Flow

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 59

Chiller #5 Flow

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 60

Chiller #6 Flow

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 61

Chiller #1 DP

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 62

Chiller #2 DP

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 63

Chiller #3 DP

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 64

Chiller #4 DP

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 65

Chiller #5 DP

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)

Analog Value, 66

Chiller #6 DP

ANALOG_VALUE

0 to Span (in Technologic User Setup Menu)