Appendix h - metasys n2 communications points – Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual
Page 47

47
Appendix H - Metasys N2 Communications Points
NPT
NPA
POINT DESCRIPTION
RANGE/VALUE
UNIT
BI
1
Pump #1 Overload Failure
1 = Failure
0 = O.K.
BI
2
Pump #1 Failure
1 = Failure
0 = O.K.
BI
3
Pump #1 AFD Failure
1 = Failure
0 = O.K.
BI
4
Pump #1 Off Alarm
1 = Alarm
0 = O.K.
BI
5
Pump #2 Overload Failure
1 = Failure 0 = O.K.
BI
6
Pump #2 Failure
1 = Failure 0 = O.K.
BI
7
Pump #2 AFD Failure
1 = Failure 0 = O.K.
BI
8
Pump #2 Off Alarm
1 = Alarm
0 = O.K.
BI
9
Pump #3 Overload Failure
1 = Failure 0 = O.K.
BI
10
Pump #3 Failure
1 = Failure 0 = O.K.
BI
11
Pump #3 AFD Failure
1 = Failure 0 = O.K.
BI
12
Pump #3 Off Alarm
1 = Alarm
0 = O.K.
BI
13
Pump #4 Overload Failure
1 = Failure
0 = O.K.
BI
14
Pump #4 Failure
1 = Failure 0 = O.K.
BI
15
Pump #4 AFD Failure
1 = Failure
0 = O.K.
BI
16
Pump #4 Off Alarm
1 = Alarm
0 = O.K.
BI
17
Pump #5 Overload Failure
1 = Failure 0 = O.K.
BI
18
Pump #5 Failure
1 = Failure 0 = O.K.
BI
19
Pump #5 AFD Failure
1 = Failure 0 = O.K.
BI
20
Pump #5 Off Alarm
1 = Alarm
0 = O.K.
BI
21
Pump #6 Overload Failure
1 = Failure 0 = O.K.
BI
22
Pump #6 Failure
1 = Failure 0 = O.K.
BI
23
Pump #6 AFD Failure
1 = Failure 0 = O.K.
BI
24
Pump #6 Off Alarm
1 = Alarm
0 = O.K.
BI
25
System Reset Required
1 = Yes
0 = No
BI
26
Pump #1 Enabled
1 = Enabled 0 = Disabled
BI
27
Pump #1 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
28
Pump #1 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
29
Pump #2 Enabled
1 = Enabled 0 = Disabled
BI
30
Pump #2 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
31
Pump #2 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
32
Pump #3 Enabled
1 = Enabled 0 = Disabled
BI
33
Pump #3 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
34
Pump #3 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
35
Pump #4 Enabled
1 = Enabled 0 = Disabled
BI
36
Pump #4 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
37
Pump #4 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
38
Pump #5 Enabled
1 = Enabled 0 = Disabled
BI
39
Pump #5 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
40
Pump #5 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
41
Pump #6 Enabled
1 = Enabled 0 = Disabled
BI
42
Pump #6 Running In Variable Speed Mode
1 = In VSM 0 = Not In VSM
BI
43
Pump #6 Running In Bypass Mode
1 = In Bypass 0 = Not In Bypass
BI
44
Pump #1 On/Off
1 = On 0 = Off
BI
45
Pump #2 On/Off
1 = On 0 = Off
BI
46
Pump #3 On/Off
1 = On 0 = Off
BI
47
Pump #4 On/Off
1 = On 0 = Off
BI
48
Pump #5 On/Off
1 = On 0 = Off
BI
49
Pump #6 On/Off
1 = On 0 = Off