Appendix G (cont'd.)

SNVT

NV

Length

Index

Name

SNVT Type

(bytes)

POINT DESCRIPTION

RANGE/VALUE

Unit

47

nvoPmp5_On_Off

SNVT_switch(95)

2

Pump #5 On/Off

1 = On 0 = Off

48

nvoPmp6_On_Off

SNVT_switch(95)

2

Pump #6 On/Off

1 = On 0 = Off

49

nvoSys_Start_Sto

SNVT_switch(95)

2

System Start/Stop

1 = Start 0 = Stop

50

nvoAnIn1_Fail

SNVT_switch(95)

2

Analog Input #1 Failure

1 = Failure 0 = O.K.

51

nvoAnIn2_Fail

SNVT_switch(95)

2

Analog Input #2 Failure

1 = Failure 0 = O.K.

52

nvoAnIn3_Fail

SNVT_switch(95)

2

Analog Input #3 Failure

1 = Failure 0 = O.K.

53

nvoAnIn4_Fail

SNVT_switch(95)

2

Analog Input #4 Failure

1 = Failure 0 = O.K.

54

nvoAnIn5_Fail

SNVT_switch(95)

2

Analog Input #5 Failure

1 = Failure 0 = O.K.

55

nvoAnIn6_Fail

SNVT_switch(95)

2

Analog Input #6 Failure

1 = Failure 0 = O.K.

56

nvoAnIn7_Fail

SNVT_switch(95)

2

Analog Input #7 Failure

1 = Failure 0 = O.K.

57

nvoAnIn8_Fail

SNVT_switch(95)

2

Analog Input #8 Failure

1 = Failure 0 = O.K.

58

nvoAnIn9_Fail

SNVT_switch(95)

2

Analog Input #9 Failure

1 = Failure 0 = O.K.

59

nvoAnIn10_Fail

SNVT_switch(95)

2

Analog Input #10 Failure

1 = Failure 0 = O.K.

60

nvoAnIn11_Fail

SNVT_switch(95)

2

Analog Input #11 Failure

1 = Failure 0 = O.K.

61

nvoAnIn12_Fail

SNVT_switch(95)

2

Analog Input #12 Failure

1 = Failure 0 = O.K.

62

nvoAnIn13_Fail

SNVT_switch(95)

2

Analog Input #13 Failure

1 = Failure 0 = O.K.

63

nvoAnIn14_Fail

SNVT_switch(95)

2

Analog Input #14 Failure

1 = Failure 0 = O.K.

64

nvoAnIn15_Fail

SNVT_switch(95)

2

Analog Input #15 Failure

1 = Failure 0 = O.K.

65

nvoAnIn16_Fail

SNVT_switch(95)

2

Analog Input #16 Failure

1 = Failure 0 = O.K.

66

nvoIso_Valve1

SNVT_switch(95)

2

Isolation Valve 1 Feedback

1 = Closed 0 = Open

67

nvoIso_Valve2

SNVT_switch(95)

2

Isolation Valve 2 Feedback

1 = Closed 0 = Open

68

nvoIso_Valve3

SNVT_switch(95)

2

Isolation Valve 3 Feedback

1 = Closed 0 = Open

69

nvoIso_Valve4

SNVT_switch(95)

2

Isolation Valve 4 Feedback

1 = Closed 0 = Open

70

nvoIso_Valve5

SNVT_switch(95)

2

Isolation Valve 5 Feedback

1 = Closed 0 = Open

71

nvoIso_Valve6

SNVT_switch(95)

2

Isolation Valve 6 Feedback

1 = Closed 0 = Open

72

nvoReq_Stg_Chil

SNVT_switch(95)

2

Request to stage chiller

1 = Active 0 = Inactive

73

nvoReq_Dstg_Chil

SNVT_switch(95)

2

Request to destage chiller

1 = Active 0 = Inactive

74

nvoGeneral_Alarm

SNVT_switch(95)

2

General Alarm

1 = Alarm 0 = O.K.

75

nvoPV_1

SNVT_press_p (113)

2

Process Variable #1

0 to Span (in Technologic User Setup Menu)

76

nvoPV_2

SNVT_press_p (113)

2

Process Variable #2

0 to Span (in Technologic User Setup Menu)

77

nvoPV_3

SNVT_press_p (113)

2

Process Variable #3

0 to Span (in Technologic User Setup Menu)

78

nvoPV_4

SNVT_press_p (113)

2

Process Variable #4

0 to Span (in Technologic User Setup Menu)

79

nvoPV_5

SNVT_press_p (113)

2

Process Variable #5

0 to Span (in Technologic User Setup Menu)

80

nvoPV_6

SNVT_press_p (113)

2

Process Variable #6

0 to Span (in Technologic User Setup Menu)

81

nvoPV_7

SNVT_press_p (113)

2

Process Variable #7

0 to Span (in Technologic User Setup Menu)

82

nvoPV_8

SNVT_press_p (113)

2

Process Variable #8

0 to Span (in Technologic User Setup Menu)

83

nvoPV_9

SNVT_press_p (113)

2

Process Variable #9

0 to Span (in Technologic User Setup Menu)

84

nvoPV_10

SNVT_press_p (113)

2

Process Variable #10

0 to Span (in Technologic User Setup Menu)

85

nvoPV_11

SNVT_press_p (113)

2

Process Variable #11

0 to Span (in Technologic User Setup Menu)

86

nvoPV_12

SNVT_press_p (113)

2

Process Variable #12

0 to Span (in Technologic User Setup Menu)

87

nvoPV_13

SNVT_press_p (113)

2

Process Variable #13

0 to Span (in Technologic User Setup Menu)

88

nvoPV_14

SNVT_press_p (113)

2

Process Variable #14

0 to Span (in Technologic User Setup Menu)

89

nvoPV_15

SNVT_press_p (113)

2

Process Variable #15

0 to Span (in Technologic User Setup Menu)

90

nvoPV_16

SNVT_press_p (113)

2

Process Variable #16

0 to Span (in Technologic User Setup Menu)

91

nvo_System_Flow

SNVT_flow (15)

2

Totalized system flow

0 to Span (in Technologic User Setup Menu)

GPM

92

nvo_Reserved

SNVT_flow (15)

2

Not used

93

nvo_SysKW

SNVT_power_kilo (15)

2

System KW

0 to Span (in Technologic User Setup Menu)

KW