Appendix g (cont'd.) – Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual
Page 45

45
Appendix G (cont'd.)
SNVT
NV
Length
Index
Name
SNVT Type
(bytes)
POINT DESCRIPTION
RANGE/VALUE
Unit
94
nvo_KW1
SNVT_power_kilo (15)
2
KW #1
0 to Span (in Technologic User Setup Menu)
KW
95
nvo_KW2
SNVT_power_kilo (15)
2
KW #2
0 to Span (in Technologic User Setup Menu)
KW
96
nvo_KW3
SNVT_power_kilo (15)
2
KW #3
0 to Span (in Technologic User Setup Menu)
KW
97
nvo_KW4
SNVT_power_kilo (15)
2
KW #4
0 to Span (in Technologic User Setup Menu)
KW
98
nvo_KW5
SNVT_power_kilo (15)
2
KW #5
0 to Span (in Technologic User Setup Menu)
KW
99
nvo_KW6
SNVT_power_kilo (15)
2
KW #6
0 to Span (in Technologic User Setup Menu)
KW
100
nvoSys_DP
SNVT_press_p (113)
2
System Differential Pressure
0 to Span (in Technologic User Setup Menu)
PSI
101
nvoSupply_Temp
SNVT_temp (39)
2
System Supply Temperature
0 to Span (in Technologic User Setup Menu)
F°
102
nvoReturn_Temp
SNVT_temp (39)
2
System Return Temperature
0 to Span (in Technologic User Setup Menu)
F°
103
nvoSet_Pt1
SNVT_press_p (113)
2
Setpoint #1
0 to Span (in Technologic User Setup Menu)
104
nvoSet_Pt2
SNVT_press_p (113)
2
Setpoint #2
0 to Span (in Technologic User Setup Menu)
105
nvoSet_Pt3
SNVT_press_p (113)
2
Setpoint #3
0 to Span (in Technologic User Setup Menu)
106
nvoSet_Pt4
SNVT_press_p (113)
2
Setpoint #4
0 to Span (in Technologic User Setup Menu)
107
nvoSet_Pt5
SNVT_press_p (113)
2
Setpoint #5
0 to Span (in Technologic User Setup Menu)
108
nvoSet_Pt6
SNVT_press_p (113)
2
Setpoint #6
0 to Span (in Technologic User Setup Menu)
109
nvoSet_Pt7
SNVT_press_p (113)
2
Setpoint #7
0 to Span (in Technologic User Setup Menu)
110
nvoSet_Pt8
SNVT_press_p (113)
2
Setpoint #8
0 to Span (in Technologic User Setup Menu)
111
nvoSet_Pt9
SNVT_press_p (113)
2
Setpoint #9
0 to Span (in Technologic User Setup Menu)
112
nvoSet_Pt10
SNVT_press_p (113)
2
Setpoint #10
0 to Span (in Technologic User Setup Menu)
113
nvoSet_Pt11
SNVT_press_p (113)
2
Setpoint #11
0 to Span (in Technologic User Setup Menu)
114
nvoSet_Pt12
SNVT_press_p (113)
2
Setpoint #12
0 to Span (in Technologic User Setup Menu)
115
nvoSet_Pt13
SNVT_press_p (113)
2
Setpoint #13
0 to Span (in Technologic User Setup Menu)
116
nvoSet_Pt14
SNVT_press_p (113)
2
Setpoint #14
0 to Span (in Technologic User Setup Menu)
117
nvoSet_Pt15
SNVT_press_p (113)
2
Setpoint #15
0 to Span (in Technologic User Setup Menu)
118
nvoSet_Pt16
SNVT_press_p (113)
2
Setpoint #16
0 to Span (in Technologic User Setup Menu)
119
nvoPump1_Speed
SNVT_count (8)
2
Pump1 Speed %
0 to 100
%
120
nvoPump2_Speed
SNVT_count (8)
2
Pump2 Speed %
0 to 100
%
121
nvoPump3_Speed
SNVT_count (8)
2
Pump3 Speed %
0 to 100
%
122
nvoPump4_Speed
SNVT_count (8)
2
Pump4 Speed %
0 to 100
%
123
nvoPump5_Speed
SNVT_count (8)
2
Pump5 Speed %
0 to 100
%
124
nvoPump6_Speed
SNVT_count (8)
2
Pump6 Speed %
0 to 100
%
125
nvoLead_Pmp#
SNVT_count (8)
2
Lead Pump Number
1 to Pump # (in Technologic User Setup Menu)
126
nvoActv_Zone#
SNVT_count (8)
2
Active Zone Number
1 to Zone # (in Technologic User Setup Menu)
127
nvoSys_Op_Mode
SNVT_count (8)
2
System Operation Mode
0=Manual, 1=Auto, 2=Auto Bypass, 3=Manual Bypass
128
nvoByp_Valve_Pos
SNVT_count (8)
2
Bypass Valve Position
0 - 100
%
129
nvoChiller1_Flow
SNVT_flow (15)
2
Chiller 1 Flow
0 to Span (in Technologic User Setup Menu)
130
nvoChiller2_Flow
SNVT_flow (15)
2
Chiller 2 Flow
0 to Span (in Technologic User Setup Menu)
131
nvoChiller3_Flow
SNVT_flow (15)
2
Chiller 3 Flow
0 to Span (in Technologic User Setup Menu)
132
nvoChiller4_Flow
SNVT_flow (15)
2
Chiller 4 Flow
0 to Span (in Technologic User Setup Menu)
133
nvoChiller5_Flow
SNVT_flow (15)
2
Chiller 5 Flow
0 to Span (in Technologic User Setup Menu)
134
nvoChiller6_Flow
SNVT_flow (15)
2
Chiller 6 Flow
0 to Span (in Technologic User Setup Menu)
135
nvoChiller1_DP
SNVT_press_p (113)
2
Chiller 1 Differential Pressure 0 to Span (in Technologic User Setup Menu)
136
nvoChiller2_DP
SNVT_press_p (113)
2
Chiller 2 Differential Pressure 0 to Span (in Technologic User Setup Menu)
137
nvoChiller3_DP
SNVT_press_p (113)
2
Chiller 3 Differential Pressure 0 to Span (in Technologic User Setup Menu)
138
nvoChiller4_DP
SNVT_press_p (113)
2
Chiller 4 Differential Pressure 0 to Span (in Technologic User Setup Menu)
139
nvoChiller5_DP
SNVT_press_p (113)
2
Chiller 5 Differential Pressure 0 to Span (in Technologic User Setup Menu)
140
nvoChiller6_DP
SNVT_press_p (113)