beautypg.com

Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual

Page 18

background image

18

Variable

Unit

Description

Default Value

Range

Field Value

AFD Fail

s

Proof timer prior to setting the AFD fail alarm

20

0-999

Pr Tm
Pump Fail

s

Proof timer prior to setting the pump fail alarm

30

0-999

Pr Tm
O.L. Fail

s

Proof timer prior to setting the O.L. fail alarm

3

0-999

Pr Tm
Reset Tm

s

Time delay between pressing the RESET key and

10

0-999

restarting the pumps in variable speed mode, allows
for pump deceleration

Table 13: Alarm Variables

4.3.1.4 EOC Destage

From the Stage/Destage Menu, shown in section

4.3.1, press ALTERNATION/4 and ENTER to get to
the EOC Destage screen shown below.

Destage Flow: ##%

Destage Pr Tm: ##s
Tm Forced Destg: #m

Ok ? (Y/N)

To edit the fields, press NO/0 and ENTER. To return

to the Stage/Destage Menu, shown in section 4.3.1,
press YES/7 and ENTER. See Table 11 below for a
description of the EOC Destage variables.

4.3.2

PID

From the System Setup Menu, shown in section 4.3,

press SETPOINT/2 and ENTER to get to the PID
screen shown below.

PID-P ### PID-I #

PID-D #
Ramp Timer ###s

Ok ? (Y/N)

To edit the fields, press NO/0 and ENTER. To return

to the System Setup Menu, shown in section 4.3,
press YES/7 and ENTER. See Table 12 below for a
description of the PID variables.

4.3.3

Alarms Setup

From the System Setup Menu, shown in section 4.3,

press SETUP/3 and ENTER to get to the Alarms
Setup screen shown below.

AFD Fail Pr Tm: ##s

Pump Fail Pr Tm: ##s
O.L. Fail Pr Tm: ##s
Reset Tm: 10s Ok ? YN

To return to the System Setup Menu, shown in sec

-

tion 4.3, press YES/7 and ENTER. To edit the fields,
press NO/0 and ENTER. See Table 13 for a descrip-
tion of the Alarms Setup variables.

4.3.4

Alternation Setup

From the System Setup Menu, shown in section 4.3,

press ALTERNATION/4 and ENTER to get to the
Alternation Setup screen shown below.

Time Between: # Hr.

Duration: ##s

Ok ? YN

To return to the System Setup Menu, shown in sec

-

tion 4.3, press YES/7 and ENTER. To edit the fields,
press NO/0 and ENTER. See Table 14 on next page
for a description of the Alternation Setup variables.

Note: Alternation can also be accomplished manually.

See section 5.10.

Variable

Unit

Description

Default Value

Range

Field Value

PID-P

N/A

Proportional value

200

0-999

PID-I

N/A

Integral value

5

0-999

PID-D

N/A

Derivative value

2

0-999

Ramp

s

The amount of time it takes to get a pump up to full speed

100

25-100

Timer

immediately after starting a chiller. This variable only
applies to dedicated pump to chiller systems.

Table 12: PID Variables

Variable

Unit

Description

Default Value

Range

Field Value

Destage

%

Percentage of max flow at which the lag pump is

45

0-100

Flow

destaged

Destage

s

Proof timer prior to destaging lag pump

30

0-999

Pr Tm
Tm

m

Time elapsed before a forced destage

0

0-100

Forced
Destg

Table 11: EOC

Destage Variables