Appendix H (cont'd.)

NPT

NPA

POINT DESCRIPTION

RANGE/VALUE

UNIT

ADI

19

System KW

0 to Span (in Technologic User Setup Menu)

KW

ADI

20

Pump #1 Power

0 to Span (in Technologic User Setup Menu)

KW

ADI

21

Pump #2 Power

0 to Span (in Technologic User Setup Menu)

KW

ADI

22

Pump #3 Power

0 to Span (in Technologic User Setup Menu)

KW

ADI

23

Pump #4 Power

0 to Span (in Technologic User Setup Menu)

KW

ADI

24

Pump #5 Power

0 to Span (in Technologic User Setup Menu)

KW

ADI

25

Pump #6 Power

0 to Span (in Technologic User Setup Menu)

KW

ADI

26

System Differential Pressure

0 to Span (in Technologic User Setup Menu)

PSI

ADI

27

Supply Temperature Sensor

0 to Span (in Technologic User Setup Menu)

ADI

28

Return Temperature Sensor

0 to Span (in Technologic User Setup Menu)

ADI

29

Setpoint #1

0 to Span (in Technologic User Setup Menu)

ADI

30

Setpoint #2

0 to Span (in Technologic User Setup Menu)

ADI

31

Setpoint #3

0 to Span (in Technologic User Setup Menu)

ADI

32

Setpoint #4

0 to Span (in Technologic User Setup Menu)

ADI

33

Setpoint #5

0 to Span (in Technologic User Setup Menu)

ADI

34

Setpoint #6

0 to Span (in Technologic User Setup Menu)

ADI

35

Setpoint #7

0 to Span (in Technologic User Setup Menu)

ADI

36

Setpoint #8

0 to Span (in Technologic User Setup Menu)

ADI

37

Setpoint #9

0 to Span (in Technologic User Setup Menu)

ADI

38

Setpoint #10

0 to Span (in Technologic User Setup Menu)

ADI

39

Setpoint #11

0 to Span (in Technologic User Setup Menu)

ADI

40

Setpoint #12

0 to Span (in Technologic User Setup Menu)

ADI

41

Setpoint #13

0 to Span (in Technologic User Setup Menu)

ADI

42

Setpoint #14

0 to Span (in Technologic User Setup Menu)

ADI

43

Setpoint #15

0 to Span (in Technologic User Setup Menu)

ADI

44

Setpoint #16

0 to Span (in Technologic User Setup Menu)

ADI

45

Pump #1 Speed

0 to 100

%

ADI

46

Pump #2 Speed

0 to 100

%

ADI

47

Pump #3 Speed

0 to 100

%

ADI

48

Pump #4 Speed

0 to 100

%

ADI

49

Pump #5 Speed

0 to 100

%

ADI

50

Pump #6 Speed

0 to 100

%

ADI

51

Lead Pump Number

1 to Pump # (in Technologic User Setup Menu)

ADI

52

Active Zone Number

1 to Zone # (in Technologic User Setup Menu)

ADI

53

System Operation Mode

0=Manual,1=Auto, 2=Auto Bypass, 3=Manual Bypass

ADI

54

Bypass Valve Position

0 to 100, 0 = Closed 100 = Open

%

ADI

55

Chiller #1 Flow

0 to Span (in Technologic User Setup Menu)

ADI

56

Chiller #2 Flow

0 to Span (in Technologic User Setup Menu)

ADI

57

Chiller #3 Flow

0 to Span (in Technologic User Setup Menu)

ADI

58

Chiller #4 Flow

0 to Span (in Technologic User Setup Menu)

ADI

59

Chiller #5 Flow

0 to Span (in Technologic User Setup Menu)

ADI

60

Chiller #6 Flow

0 to Span (in Technologic User Setup Menu)

ADI

61

Chiller #1 DP

0 to Span (in Technologic User Setup Menu)

ADI

62

Chiller #2 DP

0 to Span (in Technologic User Setup Menu)

ADI

63

Chiller #3 DP

0 to Span (in Technologic User Setup Menu)

ADI

64

Chiller #4 DP

0 to Span (in Technologic User Setup Menu)

ADI

65

Chiller #5 DP

0 to Span (in Technologic User Setup Menu)

ADI

66

Chiller #6 DP

0 to Span (in Technologic User Setup Menu)