Page 23

background image

23

4.3.10.4

BACnet/IP

From the Communication Setup Menu, shown in sec

-

tion 4.3.10, press ALTERNATION/4 and ENTER to get
to the BACnet/IP screen shown below.

IP Address:

###. ###. ###. ###
Subnet:
###. ###. ###. ###

BACnet device IP address and Subnet is provided by

building management system. Press NEXT SCREEN
and the display will show:

Inst. # #### Delay ##

Setpoint Ovrd ?(Y/N)
Save IPAdd. ?(Y/N)

Exit ? (Y/N)

To return to the Communications Setup Menu, shown

in section 4.3.10, press YES/7 and ENTER. To edit
the fields, press NO/0 and ENTER. Table 25 gives a
description of the BACnet/IP Variables.

For additional information concerning the above pro-
tocols, consult the Bell & Gossett Technologic 5500
Serial Communications instruction manual (part num-
ber S13654).

Contact your Bell & Gossett representative concern-
ing additional protocols and setups.

4.3.11

Special Functions

From the System Setup Menu, shown in section 4.3,

press 11 and ENTER to get to the Special Functions
Menu shown below.

Selection: # 0 = Exit

1 = Pump Duty/Standby

Press PROCESS VARIABLE/1 and ENTER to get to

the Pump Duty/Standby screen shown below, or
press NO/0 to exit back to the System Setup Menu
shown in section 4.3.

# of Duty Pump #

# of Standby Pump #

Exit: ? (Y/N)

Table 26, shown below, gives a description of the

Pump Duty/Standby variables.

4.3.12

Brightness/Contrast

From the System Setup Menu, shown in section 4.3,

press 12 and ENTER to get to the Brightness/Contrast
screen shown below.

Contrast is: ###

Change is: ###

Ok ? (Y/N)

To return to the System Setup Menu, shown in sec

-

tion 4.3, press YES/7 and ENTER. To edit the field,
press NO/0 and ENTER. Table 27 gives a description
of the Brightness/Contrast variables.

4.3.13

Save to Flash

From the System Setup Menu, shown in section 4.3,

press 13 and ENTER to get to the Save to Flash
screen shown below.

**WARNING**

CPU WILL BE HALTED

DATA WILL BE SAVED

PROCEED: ? (Y/N)

To return to the System Setup Menu, shown in sec

-

tion 4.3, press NO/0 and ENTER. To save all of the
user setup data to the ROM within the controller,
press YES/7 and ENTER.

Variable

Unit

Description

Default Value

Range

Field Value

Inst. #

N/A

If multiple devices are present on the network, a unique

100

0-9999

instance number is required.

Start Delay Seconds

Time delay to start the BACnet interface

10

0-999

Set Point

Select YES for the external device to override the local

N

Y/N

Ovrd

setpoint data

Save IP

Select YES to save IP address. Saving the I.P. address

N

Y/N

Add

will cause the controller to power cycle.

Table 25: BACnet/IP Variables

Variable

Description

Default Value

Range

Field Value

# of Duty Pump

Number of duty pump equals the number of pumps

0

0-6

configured in the pump setup menu minus the number of
standby pumps

# of Standby Pump

Standby pumps are those pumps that will not run unless

0

0-6

one of the duty pumps fail.

Table 26: Pump Duty/Standby Variables

Variable

Description

Default Value

Range

Field Value

Contrast is:

Current contrast setting is not modifiable (0 = Light

500

200-1000

Characters, 100 = Darkest Characters)

Change to:

Desired Contrast Setting (Setting of 1000 will reduce the

500

200-1000

life of the screen)

Table 27: Brightness/Contrast Variables