beautypg.com

Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual

Page 27

background image

27

4.7

Bypass Valve Setup

From the Setup Selection Menu, shown in section 4,

press YES/7 and ENTER to get to the Bypass Valve
Setup Menu shown below.

Selection: # Exit =0

1 = Byps Valve Setting
2 = Byps Operat. Mode
3 = Timers

Press the appropriate numeric key and ENTER.

4.7.1

Bypass Valve Setting

From the Bypass Valve Setup Menu, shown in sec

-

tion 4.7, press PROCESS VARIABLE/1 to get to the
Bypass Valve Setting screen shown below.

Min Opening = ##%

Max Opening = ##%
Step = ##% Volts: ?
Rev ?(Y/N) Ok ? (Y/N)

To return to the Bypass Valve Setup Menu, shown in

section 4.7, press YES/7 and ENTER. To edit the
values shown, press NO/7 and ENTER. See Table 32
for a description of the Bypass Valve Opening variables.

4.7.2

Bypass Valve Operation Mode

From the Bypass Valve Setup Menu, shown in sec

-

tion 4.7, press SET POINT/2 to get to the Bypass
Valve Operation Mode screen shown below.

Bypass Valve

Operation Mode #
1 = Auto

2 = Manual

Ok ? (Y/N)

To return to the Bypass Valve Setup Menu, shown in

section 4.7, press YES/7 and ENTER. To edit the
value shown, press NO/7 and ENTER. See Table 33
for a description of the Operation Modes.

4.7.3

Timers

From the Bypass Valve Setup Menu, shown in sec

-

tion 4.7, press SETUP/3 to get to the Timers screen
shown below.

Bypass Valve Timers

Opening Timer ##s
Closing Timer ## s

Ok ?

To return to the Bypass Valve Setup Menu, shown in

section 4.7, press YES/7 and ENTER. To edit the
values shown, press NO/7 and ENTER. See Table 34
for a description of the Timer variables.

Variable

Unit

Description

Default Value

Range

Field Value

Min

%

Minimum Valve Position

0

0-100

Opening
Max

%

Maximum Valve Position

100

0-100

Opening
Step

%

The increment by which the valve will modulate

3

0-100

Volts

N/A

Select "Y" if the signal to the bypass valve is 0-10V.

N

Y/N

Select "N" if the signal is 4-20mA.

Rev

N/A

Select "N" if the signal to the bypass valve is not

N

Y/N

reversed (4mA or 0V = closed, 20mA or 10V = open),
Select "Y" if the signal to the bypass valve is reversed
(20mA or 10V = closed, 4mA or 0V = open).

Table 32: Bypass Valve Opening Variables

Table 33: Bypass Valve Operation Modes

Variable

Unit

Description

Default Value

Range

Field Value

Opening

s

Time delay between opening the bypass valve by

3

0-30

Timer

the Step.

Closing

s

Time delay between closing the bypass valve by

5

0-30

Timer

the Step.

Variable

Description

Default Value

Range

Field Value

Bypass Valve

Select "1" for automatic operation. In automatic operation

1

1,2

Operation Mode

the Logic controls the valve opening to protect the chiller
minimum flow. Select "2" for manual operation. In manual
operation use the Bypass Valve Position screen, shown in
section 5.1.10, to control valve position.

Table 34: Timers Variables