Appendix h (cont'd.) – Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual
Page 48

48
Appendix H (cont'd.)
NPT
NPA
POINT DESCRIPTION
RANGE/VALUE
UNIT
BI
50
System Start/Stop
1 = Start 0 = Stop
BI
51
Analog Input #1 Failure
1 = Failure 0 = O.K.
BI
52
Analog Input #2 Failure
1 = Failure 0 = O.K.
BI
53
Analog Input #3 Failure
1 = Failure 0 = O.K.
BI
54
Analog Input #4 Failure
1 = Failure 0 = O.K.
BI
55
Analog Input #5 Failure
1 = Failure 0 = O.K.
BI
56
Analog Input #6 Failure
1 = Failure 0 = O.K.
BI
57
Analog Input #7 Failure
1 = Failure 0 = O.K.
BI
58
Analog Input #8 Failure
1 = Failure 0 = O.K.
BI
59
Analog Input #9 Failure
1 = Failure 0 = O.K.
BI
60
Analog Input #10 Failure
1 = Failure 0 = O.K.
BI
61
Analog Input #11 Failure
1 = Failure 0 = O.K.
BI
62
Analog Input #12 Failure
1 = Failure 0 = O.K.
BI
63
Analog Input #13 Failure
1 = Failure 0 = O.K.
BI
64
Analog Input #14 Failure
1 = Failure 0 = O.K.
BI
65
Analog Input #15 Failure
1 = Failure 0 = O.K.
BI
66
Analog Input #16 Failure
1 = Failure 0 = O.K.
BI
67
Isolaion Valve #1
1 = Open 0 = Closed
BI
68
Isolaion Valve #2
1 = Open 0 = Closed
BI
69
Isolaion Valve #3
1 = Open 0 = Closed
BI
70
Isolaion Valve #4
1 = Open 0 = Closed
BI
71
Isolaion Valve #5
1 = Open 0 = Closed
BI
72
Isolaion Valve #6
1 = Open 0 = Closed
BI
73
Request to Stage Chiller
1 = Yes
0 = No
BI
74
Request to De-stage Chiller
1 = Yes
0 = No
BI
75
General Alarm
1 = Alarm
0 = O.K.
BO
1
Pump Sequence Alternation
1 = Yes
0 = No
BO
2
System Reset Request
1 = Yes
0 = No
BO
3
System Start / Stop
1 = Start 0 = Stop
ADI
1
Process Variable #1
0 to Span (in Technologic User Setup Menu)
ADI
2
Process Variable #2
0 to Span (in Technologic User Setup Menu)
ADI
3
Process Variable #3
0 to Span (in Technologic User Setup Menu)
ADI
4
Process Variable #4
0 to Span (in Technologic User Setup Menu)
ADI
5
Process Variable #5
0 to Span (in Technologic User Setup Menu)
ADI
6
Process Variable #6
0 to Span (in Technologic User Setup Menu)
ADI
7
Process Variable #7
0 to Span (in Technologic User Setup Menu)
ADI
8
Process Variable #8
0 to Span (in Technologic User Setup Menu)
ADI
9
Process Variable #9
0 to Span (in Technologic User Setup Menu)
ADI
10
Process Variable #10
0 to Span (in Technologic User Setup Menu)
ADI
11
Process Variable #11
0 to Span (in Technologic User Setup Menu)
ADI
12
Process Variable #12
0 to Span (in Technologic User Setup Menu)
ADI
13
Process Variable #13
0 to Span (in Technologic User Setup Menu)
ADI
14
Process Variable #14
0 to Span (in Technologic User Setup Menu)
ADI
15
Process Variable #15
0 to Span (in Technologic User Setup Menu)
ADI
16
Process Variable #16
0 to Span (in Technologic User Setup Menu)
ADI
17
System Flow
0 to Span (in Technologic User Setup Menu)
GPM
ADI
18
Reserved
0 to Span (in Technologic User Setup Menu)