Appendix h (cont'd.) – Bell & Gossett S14334B Technologic 5500 Series Variable Primary Pump and Valve Controller User Manual

Page 48

background image

48

Appendix H (cont'd.)

NPT

NPA

POINT DESCRIPTION

RANGE/VALUE

UNIT

BI

50

System Start/Stop

1 = Start 0 = Stop

BI

51

Analog Input #1 Failure

1 = Failure 0 = O.K.

BI

52

Analog Input #2 Failure

1 = Failure 0 = O.K.

BI

53

Analog Input #3 Failure

1 = Failure 0 = O.K.

BI

54

Analog Input #4 Failure

1 = Failure 0 = O.K.

BI

55

Analog Input #5 Failure

1 = Failure 0 = O.K.

BI

56

Analog Input #6 Failure

1 = Failure 0 = O.K.

BI

57

Analog Input #7 Failure

1 = Failure 0 = O.K.

BI

58

Analog Input #8 Failure

1 = Failure 0 = O.K.

BI

59

Analog Input #9 Failure

1 = Failure 0 = O.K.

BI

60

Analog Input #10 Failure

1 = Failure 0 = O.K.

BI

61

Analog Input #11 Failure

1 = Failure 0 = O.K.

BI

62

Analog Input #12 Failure

1 = Failure 0 = O.K.

BI

63

Analog Input #13 Failure

1 = Failure 0 = O.K.

BI

64

Analog Input #14 Failure

1 = Failure 0 = O.K.

BI

65

Analog Input #15 Failure

1 = Failure 0 = O.K.

BI

66

Analog Input #16 Failure

1 = Failure 0 = O.K.

BI

67

Isolaion Valve #1

1 = Open 0 = Closed

BI

68

Isolaion Valve #2

1 = Open 0 = Closed

BI

69

Isolaion Valve #3

1 = Open 0 = Closed

BI

70

Isolaion Valve #4

1 = Open 0 = Closed

BI

71

Isolaion Valve #5

1 = Open 0 = Closed

BI

72

Isolaion Valve #6

1 = Open 0 = Closed

BI

73

Request to Stage Chiller

1 = Yes

0 = No

BI

74

Request to De-stage Chiller

1 = Yes

0 = No

BI

75

General Alarm

1 = Alarm

0 = O.K.

BO

1

Pump Sequence Alternation

1 = Yes

0 = No

BO

2

System Reset Request

1 = Yes

0 = No

BO

3

System Start / Stop

1 = Start 0 = Stop

ADI

1

Process Variable #1

0 to Span (in Technologic User Setup Menu)

ADI

2

Process Variable #2

0 to Span (in Technologic User Setup Menu)

ADI

3

Process Variable #3

0 to Span (in Technologic User Setup Menu)

ADI

4

Process Variable #4

0 to Span (in Technologic User Setup Menu)

ADI

5

Process Variable #5

0 to Span (in Technologic User Setup Menu)

ADI

6

Process Variable #6

0 to Span (in Technologic User Setup Menu)

ADI

7

Process Variable #7

0 to Span (in Technologic User Setup Menu)

ADI

8

Process Variable #8

0 to Span (in Technologic User Setup Menu)

ADI

9

Process Variable #9

0 to Span (in Technologic User Setup Menu)

ADI

10

Process Variable #10

0 to Span (in Technologic User Setup Menu)

ADI

11

Process Variable #11

0 to Span (in Technologic User Setup Menu)

ADI

12

Process Variable #12

0 to Span (in Technologic User Setup Menu)

ADI

13

Process Variable #13

0 to Span (in Technologic User Setup Menu)

ADI

14

Process Variable #14

0 to Span (in Technologic User Setup Menu)

ADI

15

Process Variable #15

0 to Span (in Technologic User Setup Menu)

ADI

16

Process Variable #16

0 to Span (in Technologic User Setup Menu)

ADI

17

System Flow

0 to Span (in Technologic User Setup Menu)

GPM

ADI

18

Reserved

0 to Span (in Technologic User Setup Menu)