Directions to Configure Temperature System
1. Wire temperature sensor to 5X00 I/O Board (for non ODO sensor
temperature system) - page 54.
2. Configure “temperature” input type (for non ODO sensor temperature
system) at
Menus → System → Configure Aux →Input Type
3. Configure temperature source :
Menus → Sensor Setup→ DO 1-4→Temp Source→User Defined
→Aux
1-6
OR
M
enus → System → Configure (Aux 3-6 only) →Temp Source →Aux Input
→ODO Probe
5400
5500
4. Enter Aux 3-6 in Sensor Setup menu to configure temperature system:
Menus → System → Sensor Setup→Aux 3-6 (Temperature 1-6)
5. Configure Control Mode see page 138.
Menus → System → Sensor Setup
→Set Point Control
→PID/PWM Control
6. Use
▲
▼
to scroll and highlight submenus.
7.
Press
to select.
8. Configure submenus.
9. Press
to save settings and return to Run Screen.
Notes:
- It is important to keep the 5X00 at the Run Screen during normal opera-
tion. Alarm functionality (email alarms, activation of enabled alarm relays,
alarm icons, and buzzer) is suspended when 5X00 is not at Run Screen.
- The Configure Aux menu will display temperature configured channels as
“disabled”. This is because aux systems configured as temperature channels no
longer function as analog aux channels, but rather function as a temperature
sensor system.
- The Sensor Setup menu - page 138 is automatically enabled when an aux
channel is configured for temperature.
Configuring the 5X00
Configuring the 5X00