Dc distribution panels, Table 9-f: dc distribution panels – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual
Page 70

Galaxy Power System 4848/100 with Dual Rectifier Shelf
9 - 8 Specifications
Issue 5 September 2011
DC Distribution Panels
Table 9-F: DC Distribution Panels
Fuse or CB
Pos
Height
(in.)
LVLD
Shunt
ED83143-31
Group
1
H569-434
GPS 4848/100 Group
1
CB Clip-on / Fuse Small - TPA
14
6
11
40, 40A, 50, 50A
CB Clip-on / Fuse Small - TPA
14
6
Y
11
45, 45A, 55, 55A
CB Clip-on / Fuse Small - TPA
22
9
12
41, 41A, 51, 51A
CB Clip-on / Fuse Small - TPA
22
9
Y
12
46, 46A, 56, 56A
CB Large – Bolt-in
3
6
CB size, 25mV
2
42, 42A, 106, 106A, 107,
107A, 108, 108A, 109, 109A
CB Large – Bolt-in
3
6
Y
CB size, 25mV
2
47, 47A
CB Large – Bolt-in
5
9
CB size, 25mV
5
48, 48A, 110, 110A, 111,
111A, 112, 112A, 113, 113A
CB Large – Bolt-in
5
9
Y
CB size, 25mV
5
48B, 48C
CB Large – Bolt-in
6
12
CB size, 25mV
1
43, 43A, 101, 101A, 102,
102A, 103, 103A, 104, 104A
CB Large – Bolt-in
6
12
Y
CB size, 25mV
1
43B, 43C
CB Bullet
10
6
15
96, 96A
CB Bullet
10
6
Y
15
96B, 96C
CB Bullet
14
6
16
97, 97A
CB Bullet
14
6
Y
16
97B, 97C
CB Bullet
22
9
17
98, 98A
CB Bullet
22
9
Y
17
98B, 98C
Fuse Medium - TPS
10
6
53
52, 52A
Fuse Medium - TPS
10
6
Y
53
52B, 52C
Fuse Large
2
6
1500A, 50mV
1 / fuse
56, 56A
59, 59A
Fuse Large - TPL
2
9
600A, 50mV
1 / fuse
55
53, 53A
Fuse Large - TPL
2
9
Y
600A, 50mV
1 / fuse
55
57, 57A
Fuse Large - TPL-B
5
9
300A, 50mV
1 / fuse
54
54, 54A
Fuse Large - TPL-B
5
9
Y
300A, 50mV
1 / fuse
54
54B, 54C
CB DIN Small
14
6
71/171
60, 60A
CB DIN Small
14
6
Y
71/171
60B, 60C
CB DIN Large
10
6
71/171
61, 61A
CB DIN Large
10
6
Y
71/171
61B, 61C
Fuse DIN 10 x 38mm
14
6
71/171
65, 65A
Fuse DIN 10 x 38mm
14
6
Y
71/171
65B, 65C
Fuse DIN 14 x 51mm
10
6
71/171
66, 66A
Fuse DIN 14 x 51mm
10
6
Y
71/171
66B, 66C
Fuse DIN NH00
8
6
22
67, 67A
Fuse DIN NH00
8
6
Y
22
67B, 67C
Fuse DIN NH2
2
6
21
68, 68A
Fuse DIN NH2
2
6
Y
21
68B, 68C
Small Fuse, 6-GMT
6
0
58
58
Blank Panel
-
3
JD
93
Blank Panel
-
6
JA
90
Blank Panel
-
9
JB
91
Blank Panel
-
12
JC
92
1. Groups with B suffix or no suffix include return bus.
Groups with A or C suffix and Blank Panels do not include return bus.