Galaxy Power System 4848/100 with Dual Rectifier Shelf
4 - 2 Rectifiers
Issue 5 September 2011
Front Panel Display
Power Switch
This three-position switch has two functions:
•
It controls the on/standby state of the rectifier.
•
It is used to set the rectifier ID.
Status Indicators
In addition to the ON and STBY LEDs, four other LEDs on the
rectifier’s faceplate indicate the rectifier’s condition.
•
The ALM LED is red and lights when a thermal alarm occurs or a
rectifier fail condition occurs. This LED blinks when
communication with the plant controller is not active.
•
The LIM LED is yellow lights when the unit is in current limit.
•
The FAN ALM LED is red and lights when the fan inside the
rectifier is not functioning properly.
•
The EQL LED is yellow and lights when the rectifier is in equalize
mode.
Current Display
This display indicates the current of the rectifier. Upon specific
no-power conditions, the 3-digit display will show informative
messages.
Lamp Test
To test the LEDs on the rectifier front panel, use the Lamp Test feature
of the controller.