Bd and rm alarm leds, or no led, Table 13-f: miscellaneous alarms – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual
Page 113
Galaxy Power System 4848/100 with Dual Rectifier Shelf
Issue 5 September 2011
Troubleshooting Millennium Systems 13 - 15
BD and RM Alarm
LEDs, or No LED
Table 13-F: Miscellaneous Alarms
Controller
LED
Controller
Alarm
Status
Millennium
Controller Display
Other
Indication(s)
Possible Problem(s)
Possible Solution(s)
BD
MAJ
Battery on
Discharge
Rectifiers
may say
ACF.
Temporary
condition that may
be associated with
other alarms
Call technical support.
RM
MIN
Module Failure
Green LED
on RPM will
not blink.
Remote Peripheral
Module has failed.
Call technical support.
RM
MIN
Measurement Out
of Range
--
•Data being sensed
exceeds remote
peripheral
module’s
capability.
•Remote peripheral
module has failed.
Call technical support.
None
MAJ
Auxiliary Major
Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary equipment
Call technical support.
None
MIN
Auxiliary Minor
Auxiliary
equipment
may have
alarm.
Problem with
operation of
auxiliary equipment
Call technical support.
None
None
None
•STBY LED
on rectifier
is lit.
•TR on
rectifier
display
Remote transfer:
•Rectifier is in
STBY.
Remove the remote
standby command issued
by the controller.
None
None
None
Red LED is
lit on some
battery
contactor
drive
boards,
while green
LED is lit on
others.
If a green LED is lit
despite a contactor
open command
issued by the
controller, the drive
card or the
contactor has failed.
Call technical support.