Rectifiers, 595 series, Overview – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual
Page 35: 4 rectifiers, Overview 4-1, 4rectifiers
![background image](/manuals/295650/35/background.png)
Galaxy Power System 4848/100 with Dual Rectifier Shelf
Issue 5 September 2011
Rectifiers 4 - 1
4
Rectifiers
595 Series
Overview
Four rectifiers are available for the GPS 4848/100 system with dual
rectifier shelves: 595A Series, 595B Series, 595LTA Series, and
595LTB Series.
GPS4848/100 Rectifiers
Series
DC
Current
Rectifiers
per Shelf
3-Phase AC
Input Voltage
595A
200A
1
320-530Vac
595B
200A
1
170-260Vac
595LTA
220A
2
320-530Vac
595LTB
220A
2
170-260Vac
The rectifiers are shipped separately from the cabinets for quick and
straightforward installation into rectifier shelves at the site.
Interconnections to ac input, dc output, and control signals occur
automatically during insertion. The rectifiers are keyed to prevent
installation of a rectifier with incompatible ac input. No operational
settings or adjustments to potentiometers are necessary. The installer
must set the ID of each rectifier using its ON/STBY switch to allow the
controller to identify the rectifier for status and alarm reporting.
595A and 595B series rectifiers (full width, one per shelf) are fully
supported. See GPS 4848/100 User's Guide for views and other details
of 595A and 595B series rectifiers.